2005-12-28 00:00:00 | ********* UNSAT ********* |
| |
| 1)NOTE: PLEASE CORRELATE ELECTRICAL |
| DETAIL ON PLANS WITH THE 8 1/2X 11 |
| SUBMITTED BY EASTERN EELCTRIC WHICH |
| MENTIONS NEW PANEL ETC. |
| PLEASE SEE DETAIL DOES NOT INCLUDE THE |
| SAME INFORMATION.? |
| |
| 2)NOTE: PLEASE SEE THE PLANS REFERENCE |
| THE 2005 NEC?, PLEASE KNOW, THE STATE |
| HAS NOT YET ADOPTED THE 2005 CODE. |
| (PROBABLY NOT UNTIL OCT 2006 AT THE |
| EARLIEST). |
| |
| 3)NOTE: PLEASE SEE SURVEY SHOWS POOL |
| WITHIN 5' OF REAR PROPERTY LINE, PLEASE |
| VERIFY ANY OVER HEAD POWER LINES. ALL |
| MUST MEET MIN CLEARENCES AS SET FORTH IN |
| 680.8 PLEASE SEE THIS IS 0-750VETC AND |
| ABOVE. THIS CAN BE REDLINED, HOWEVER NOW |
| WOULD BE THE TIME TO VERIFYSINCE PLANS |
| ARE COMING BACK FOR CORRECTIONS BEFORE |
| HAVING TO MOVE A POOL AT A LATER DATE, |
| AS THE UTILITY COMPANIES WILL NOT BE |
| MOVING. |
| CONTRACTOR RESPONSIBLE TO MOVE POOL IF |
| CLOSER THAN MIN. |
| |
| 4)NOTE: PLEASE INCLUDE MIN LOAD |
| CALCULATIONS FOR ADDED LOADS. |
| PLEASE INCLUDE CONTINUOUS LOADS AT 125%. |
| 215.3,230.42, 220 ETC. |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW. |