Plan Review Notes For Permit 05120236 |
Permit Number |
05120236 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-12-15 00:00:00 | DENIED; | | 1.PLEASE SHOW A DETAIL OF A SINK IN A | | CABINET. DETAIL SHOWN IS FOR A WALL HUNG | | SINK. SHOW COMPLIANCE TO FBC-2004 | | CHAPTER 11 SEC. 11-4.24.1 THRU | | 11-4.24.7. SHOW 30" OPENING UNDER SINK | | AND HIGHT OF 34" TO TOP OF SINK. | | 2.WATER RISER DIAGRAM, CHANGE AIR | | CHAMBER TO WATER HAMMER ARRESTOR PER. | | SEC. 604.9 AND INSTALLED PER | | MANUFACTURE'S RECOMMENDATIONS, AS CLOSE | | TO SOURCE AS POSIBLE. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|