2007-11-01 08:52:17 | |
| ** DENIED REVISION** |
| |
| |
| 1) NOTE: PLEASE CLARIFY WHERE REVISION #8 IS LOCATED AS |
| LISTED ON REVISION TITLE BLOCK. |
| FBC 106.1.2 FOR COORDINATION AND ADDITIONAL |
| INFORMATION. |
| |
| 2) NOTE: PLEASE SEE RECEPTACLE ALONG KITCHEN WALL |
| WITHIN 6FT OF DOOR IS STILL MISSING PER 210.52. |
| REDLINED ON PREVIOUS PLANS. |
| |
| 3) NOTE: PLEASE SEE KITCHEN WALL RECEPTACLES STILL |
| SHOWN ON LIVING ROOM CIRCUIT WHICH IS NOT PERMITTED PER |
| 210.52B1. |
| |
| 4) NOTE: PLEASE SEE BATHS 1 AND 2 ARE BOTH SHOWN |
| CIRCUITED TOGETHER WHICH IS NOT PERMITTED PER 210.11C3. |
| MAY ONLY CIRCUIT THE RECEPTACLES TOGETHER OR IF |
| LIGHTING ETC IS ON WITH THE RECEPTACLE THEN NO OTHER |
| AREAS OR ELECTRICAL IS PERMITTED TO BE FED. MAY NOT |
| CIRCUIT AS SHOWN. |
| |
| 5) NOTE: PLEASE SEE SHEET A-2 AS THIS SHOWS PANEL AS |
| 150AMPS. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |