2007-11-01 08:52:17 
 ** DENIED REVISION**
  
  
 1) NOTE: PLEASE CLARIFY WHERE REVISION #8 IS LOCATED AS
 LISTED ON REVISION TITLE BLOCK.
 FBC 106.1.2 FOR COORDINATION AND ADDITIONAL
 INFORMATION.
  
 2) NOTE: PLEASE SEE RECEPTACLE ALONG KITCHEN WALL
 WITHIN 6FT OF DOOR IS STILL MISSING PER 210.52.
 REDLINED ON PREVIOUS PLANS.
  
 3) NOTE: PLEASE SEE KITCHEN WALL RECEPTACLES STILL
 SHOWN ON LIVING ROOM CIRCUIT WHICH IS NOT PERMITTED PER
 210.52B1.
  
 4) NOTE: PLEASE SEE BATHS 1 AND 2 ARE BOTH SHOWN
 CIRCUITED TOGETHER WHICH IS NOT PERMITTED PER 210.11C3.
 MAY ONLY CIRCUIT THE RECEPTACLES TOGETHER OR IF
 LIGHTING ETC IS ON WITH THE RECEPTACLE THEN NO OTHER
 AREAS OR ELECTRICAL IS PERMITTED TO BE FED. MAY NOT
 CIRCUIT AS SHOWN.
  
 5) NOTE: PLEASE SEE SHEET A-2 AS THIS SHOWS PANEL AS
 150AMPS.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  