2007-04-05 13:26:59 | ** UNSAT ** |
| |
| |
| 1) NOTE: PLEASE SEE RISER DIAGRAM AND PLANS DO NOT |
| MATCH. PLEASE SEE THAT THE PANEL *B* STILL DOES NOT |
| INCLUDE ANY BREAKER OR OCP FEEDING PANEL *A*.. |
| 215.5, 240.4, 310.16 |
| |
| 2) NOTE: PLEASE SEE THAT NEW SMOKE ALARM CIRCUIT |
| REQUIRES ARC FAULT PROTECTION PER 210.12. |
| PLEASE SEE THAT ALL CIRCUITS IN SLEEPING ROOMS FOR LTS, |
| SA?S , RECEPTS AND FANS ARE AFCI. |
| |
| 3) NOTE: PLEASE SEE MISSING DISCONNECTS FOR AHU?S #1 |
| AND #2. |
| 440.11 |
| |
| 3) NOTE: PLEASE SEE DISHWASHER AND DISPOSAL BOTH SEEM |
| TO SHOWN TO THE SAME DEVICE/YOKE. PLEASE SEE 210.4 AS |
| IF THIS IS INDEED AS SHOWN THEN THIS WOULD REQUIRE THE |
| BOTH OF THESE ON A 2-POLE BREAKER. |
| |
| 4) NOTE: PLEASE SEE JACUZZI TUB, PLEASE VERIFY THE |
| BREAKER AND CONDUCTOR SIZE. THE SIZE OF THE CONDUCTORS |
| WAS CHANGED TO #12 AWG, YET THE BREAKER WAS LEFT AT |
| 15AMPS? |
| PLEASE VERIFY THIS AS IT IS NOT A CODE VIOLATION ONLY A |
| COMMENT. |
| |
| 5) NOTE: PLEASE SEE THAT NO HAND-DRAWN CHANGES ARE TO |
| BE MADE TO PLANS. PLEASE SEE SEVERAL AREAS WHICH |
| HAND-WRITTEN ITEMS WERE CHANGED. |
| PLEASE REVISE THESE WHEN MAKING CORRECTIONS TO OTHER |
| COMMENTS. |
| FBC 106.1.2 |
| |
| 6) NOTE: PLEASE SEE THE PLANS ARE NOW CALLING FOR THE |
| CODES TO BE LISTED UNDER THE 2005 NEC WHEN IN FACT THIS |
| PROJECT WAS PERMITTED UNDER THE 2002 NEC. |
| PLEASE LIST THE FOLLOWING CODES. |
| 2002 NFPA-70 |
| 2002 NFPA-72 |
| |
| 7) NOTE: PLEASE SEE RECEPTACLES IN KITCHEN, DINING, |
| BREAKFAST AREAS ARE TO BE ON ONE OR MORE OF THE SMALL |
| APPLIANCE CIRCUITS. PLEASE SEE 210.52B1, 210.11C1, |
| 220.16. |
| PLEASE SEE SOME SHOWN ON THE LIGHTING CIRCUITS, THIS IS |
| NOT PERMITTED. |
| |
| 8) NOTE: PLEASE SEE THE PANEL SCHEDULE SHALL BE |
| COMPLETE WITH ALL CIRCUITS TO ROOMS AND AREAS IN WHICH |
| THEY FEED. THE USE OF *GENERAL LIGHTING * OR GEN |
| RECEPTS* IS NOT PERMITTED. |
| PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY |
| FROM THE CODE IN 408.4 |
| * |
| CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* |
| 408.4, 310.16, 240.4 ETC |
| FBC 106.3.5.4 |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |