3 |
|
Notes |
Date |
Text |
2007-02-15 09:07:09 | MECHANICAL REVISION | | *** DENIED *** | | 1) SEE NOTES: ON PLANS A/C WILL BE ACCORDING TO S.B.C. | | 2001, THE BUILDING CODES BEING USED BY THE CITY OF WEST | | PALM BEACH IS THE 2004 F.B.C., PLEASE CORRECT. | | | | 2) 12'X13" RETURN AIR DUCT FROM THE 2ND. FLOOR TO THE | | 1ST. FLOOR IS TO SMALL FOR 1535 CFM'S., PLEASE CORRECT, | | PER 2004 FBC/R M1602.4. | | | | 3) 10" RETURN AIR DUCT (FLEX) IN EXISTING FAMILY ROOM | | IS TO SMALL FOR 1125 CFM'S. AND 12'X12' GRILL, PLEASE | | CORRECT, PER 2004 FBC/R M1602.4. | | | | 4) YELLOW HIGH LIGHTED RETURN AIR TRANSFER DUCT TO | | EXISTING BEDROOM NEEDS TO BE SIZED. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|