Plan Review Notes
Plan Review Notes For Permit 05120232
Permit Number 05120232
Review Stop M
Sequence Number 3
Notes
Date Text
2007-02-15 09:07:09MECHANICAL REVISION
 *** DENIED ***
 1) SEE NOTES: ON PLANS A/C WILL BE ACCORDING TO S.B.C.
 2001, THE BUILDING CODES BEING USED BY THE CITY OF WEST
 PALM BEACH IS THE 2004 F.B.C., PLEASE CORRECT.
  
 2) 12'X13" RETURN AIR DUCT FROM THE 2ND. FLOOR TO THE
 1ST. FLOOR IS TO SMALL FOR 1535 CFM'S., PLEASE CORRECT,
 PER 2004 FBC/R M1602.4.
  
 3) 10" RETURN AIR DUCT (FLEX) IN EXISTING FAMILY ROOM
 IS TO SMALL FOR 1125 CFM'S. AND 12'X12' GRILL, PLEASE
 CORRECT, PER 2004 FBC/R M1602.4.
  
 4) YELLOW HIGH LIGHTED RETURN AIR TRANSFER DUCT TO
 EXISTING BEDROOM NEEDS TO BE SIZED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.