2007-02-09 12:48:39 | ***** UNSAT ***** |
| |
| |
| 1) NOTE: PLEASE CORRELATE THE RISER DIAGRAM WITH ALL |
| ELECTRICAL SERVICE EQUIPMENT AND PANEL SCHEDULES. |
| PLEASE SEE THERE ARE SEVERAL ITEMS WHICH DO NOT MATCH. |
| PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS FROM METER |
| TO PANEL *B* ARE NOT LARGE ENOUGH. |
| PLEASE REMOVE ANY EQUIPMENT GROUNDING CONDUCTORS BEFORE |
| THE FIRST MEANS OF DISCONNECT. (CONFUSING AS THE RISER |
| AND PLANS DO NOT MATCH). |
| PLEASE SEE MISSING EQUIPMENT GROUNDING AFTER THE FIRST |
| MEANS OF DISCONNECT. |
| PLEASE SEE 250A MAIN ON 125A PANEL. |
| PLEASE SEE LOAD ON PANEL EXCEEDS RATING. |
| PLEASE SEE PLANS WHICH DO NOT MATCH WITH RISER. |
| PLEASE SUBMIT THE PANEL SCHEDULE FOR THE METER/MAIN |
| COMBO WHICH IS MENTIONED, IF THERE IS ONE. |
| PLEASE COMPLETE AND CORRELATE LOADS ON EACH PANEL AND |
| SERVICE. |
| ETC. |
| PLEASE SEE 310.16, 310.15B6, 240.4, 240.24, 408, |
| 230.70, 230.79, 230.76 ETC. |
| |
| *THERE ARE SEVERAL ITEMS WHICH NEED TO BE CORRECTED. |
| |
| 2) NOTE: PLEASE SUBMIT A PANEL SCHEDULE WHICH REFLECTS |
| ROOM AND AREAS IN WHICH THEY FEED. |
| PLEASE SEE THE FOLLOWING TEXT WHICH WILL HELP EXPLAIN. |
| THIS REQUIRES THAT THE IDENTIFICATION FOR EVERY |
| CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| SUFFICIENT DETAIL REQUIRED BY THIS SECTION. |
| |
| 3) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE |
| SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE |
| DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE |
| DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT |
| ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER |
| THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS |
| SA/SMOKE ALARMS. |
| THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE |
| OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED. |
| BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE |
| DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL |
| NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY |
| HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF |
| SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS |
| SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS |
| SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS |
| FOR OTHER NEW HOMES. |
| ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC |
| RESIDENTIAL CODE/ FBC AND IN NFPA-72. |
| IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE. |
| |
| |
| 4) NOTE: PLEASE SEE THAT THERE ARE ELECTRICAL |
| APPLIANCES AND EQUIPMENT ON PLANS WHICH ARE NOT ON |
| PANEL SCHEDULES OR IN LOAD CALCULATIONS. |
| 240.4,310.16,220,408.4 ETC. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |