2007-02-09 12:48:39***** UNSAT *****
  
  
 1) NOTE: PLEASE CORRELATE THE RISER DIAGRAM WITH ALL
 ELECTRICAL SERVICE EQUIPMENT AND PANEL SCHEDULES.
 PLEASE SEE THERE ARE SEVERAL ITEMS WHICH DO NOT MATCH.
 PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS FROM METER
 TO PANEL *B* ARE NOT LARGE ENOUGH.
 PLEASE REMOVE ANY EQUIPMENT GROUNDING CONDUCTORS BEFORE
 THE FIRST MEANS OF DISCONNECT. (CONFUSING AS THE RISER
 AND PLANS DO NOT MATCH).
 PLEASE SEE MISSING EQUIPMENT GROUNDING AFTER THE FIRST
 MEANS OF DISCONNECT.
 PLEASE SEE 250A MAIN ON 125A PANEL.
 PLEASE SEE LOAD ON PANEL EXCEEDS RATING.
 PLEASE SEE PLANS WHICH DO NOT MATCH WITH RISER.
 PLEASE SUBMIT THE PANEL SCHEDULE FOR THE METER/MAIN
 COMBO WHICH IS MENTIONED, IF THERE IS ONE.
 PLEASE COMPLETE AND CORRELATE LOADS ON EACH PANEL AND
 SERVICE.
 ETC.
 PLEASE SEE 310.16, 310.15B6, 240.4, 240.24, 408,
 230.70, 230.79, 230.76 ETC.
  
 *THERE ARE SEVERAL ITEMS WHICH NEED TO BE CORRECTED.
  
 2) NOTE: PLEASE SUBMIT A PANEL SCHEDULE WHICH REFLECTS
 ROOM AND AREAS IN WHICH THEY FEED.
 PLEASE SEE THE FOLLOWING TEXT WHICH WILL HELP EXPLAIN.
 THIS REQUIRES THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.
  
 3) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE
 SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE
 DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
  
 4) NOTE: PLEASE SEE THAT THERE ARE ELECTRICAL
 APPLIANCES AND EQUIPMENT ON PLANS WHICH ARE NOT ON
 PANEL SCHEDULES OR IN LOAD CALCULATIONS.
 240.4,310.16,220,408.4 ETC.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  