Plan Review Notes
Plan Review Notes For Permit 05120170
Permit Number 05120170
Review Stop M
Sequence Number 3
Notes
Date Text
2006-07-19 00:00:00*** DENIED ***
 1) 5" SUPPLY AIR DUCT GOING THROUGH 1
 HOUR FIRE SEPARATION REQUIRES A METAL
 DUCT AND FIRE DAMPER, PER 2004 FBC/M 607
 . PLEASE SUBMIT DETAILED INFOMATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  