Plan Review Notes
Plan Review Notes For Permit 05120152
Permit Number 05120152
Review Stop P
Sequence Number 2
Notes
Date Text
2006-02-06 00:00:00DENIED 2ND TIME
 REFERENCE: FBC-2004 424.2 SWIMMING POOLS
  
 PLEASE ADJUST YOUR NOTES, DETAILS, OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW:
  
 1) FBC-2004 424.2.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. MANUFACTURE
 SHEETS REQUIRED. (NOTE:STILL NEED
 MANUFACTURE SHEETS WITH THIRD PARTY
 LISTING THE INFORMATION YOU HAVE
 SUBMITTED ARE SPEC SHEETS)
 2) FBC-2004 424.2.14.2 WATER RETENTION,
 PROVIDE A POSITIVE MEANS OF RETAINING
 WATER IN THE HEATER WHEN PUMP IS SHUT
 OFF.(NOTE: STILL NEED MANUFACTURE CUT
 SHEET SUBMITTAL IF ONE CANNOT BE FOUND
 AN EXTERNAL HARTFORD LOOP SHALL BE
 PROVIDED AND SHOWN ON PIPING SCHEMATIC.)
  
 END OF COMMENTS:
  