Plan Review Notes For Permit 05120152 |
Permit Number |
05120152 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-12-29 00:00:00 | DENIED | | | | REFERENCE: FBC-2004424.2 SWIMMING | | POOLS. | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR POOL PLUMBING PERMIT: | | 1) THE PIPING SCHEMATIC SHOWS ONLY ONE | | MAIN DRAIN TO THE POOL WITH A 1" VENT. | | THERE SHOULD ALSO BE A MAIN DRAIN SHOWN | | FOR THE SPA WITH A 1-1/2" VENT.PLEASE | | CORRECT THE PIPING SCHEMATIC DRAWING TO | | SHOW BOTH MAIN DRAINS ON SCHEMATIC. | | 2) COMPLY WITH FBC-2004 SEC 424.2 | | PRIVATE SWIMMING POOLS.(ADD TO NOTES) | | 3) FBC-2004 424.2.14.1 SWIMMING POOL | | WATER HEATERS SHALL BEAR THE LABEL OF A | | RECOGNIZED TESTING AGENCY. MANUFACTURE | | SHEETS REQUIRED. (SUBMITTAL) | | 4) FBC-2004 424.2.14.2 WATER RETENTION, | | PROVIDE A POSITIVE MEANS OF RETAINING | | WATER IN THE HEATER WHEN PUMP IS SHUT | | OFF. (MANUFACTURE CUT SHEETS SUBMITTAL) | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|