2006-01-17 00:00:00DENIED 2ND TIME
  
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR GAS PERMIT:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.I HAVE INCLOSED AN EXAMPLE
 OF AN ISOMETRIC DRAWING OF WHICH I THINK
 YOU ARE TRYING TO CONVEY WITH OUT THE
 MEASUREMENTS.IF THIS IS WHAT YOU ARE
 TRYING TO CONVEY FILL IN THE
 MEASUREMENTS ,SIGN, AND PRINT NAME OF
 PERSON WHO DID DRAWING AND RESUBMIT.
 NOTE, 2 COPIES REQUIRED
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561)805-6730
 FAX (561)805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561)805-6721
  