2005-12-29 00:00:00 | DENIED | | | | REFERENCE: FBC-2004 FUEL GAS | | | | THE FOLLOWING INFORMATION IS REQUIRED | | FOR A GAS PERMIT: | | 1.SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS. | | 2. SHOW TYPE OF PIPING MATERIAL BEING | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | NUMBER OF CORRUGATED STAINLESS STEEL | | TUBING FOR EACH PIPE SIZE BEING USED. | | 3. SHOW THE DISTANCE FROM THE POINT OF | | DELIVERY, (METER), TO THE MOST REMOTE | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | OF CAPACITY TABLES (A)(3). | | 4.PLEASE NOTE ON YOUR SUBMITTED DRAWING | | THAT WITH THE TOTAL AMOUNT OF BTU LOAD | | ON SYSTEM WITH THE LONGEST LENGTH METHOD | | THAT THE PIPE TO THE GENERATOR NEEDS TO | | BE 1-1/4" AND THE PIPE FROM THE METER TO | | THE GENERATOR BRANCH TEE NEEDS TO BE | | 1-1/2". REFERENCE: FBC-2004 FUEL GAS | | TABLE 402.4(2) AND TABLE 402.4(20) | | | | REVIEW BY MIKE PERSON | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|