Notes
Date Text
2005-12-29 00:00:00DENIED
  
 REFERENCE: FBC-2004 FUEL GAS
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR A GAS PERMIT:
 1.SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS.
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES (A)(3).
 4.PLEASE NOTE ON YOUR SUBMITTED DRAWING
 THAT WITH THE TOTAL AMOUNT OF BTU LOAD
 ON SYSTEM WITH THE LONGEST LENGTH METHOD
 THAT THE PIPE TO THE GENERATOR NEEDS TO
 BE 1-1/4" AND THE PIPE FROM THE METER TO
 THE GENERATOR BRANCH TEE NEEDS TO BE
 1-1/2". REFERENCE: FBC-2004 FUEL GAS
 TABLE 402.4(2) AND TABLE 402.4(20)
  