Plan Review Notes
Plan Review Notes For Permit 05120121
Permit Number 05120121
Review Stop B
Sequence Number 1
Notes
Date Text
2005-12-08 00:00:00 
 1) THIS ROOF IS MISSING OR NOT IN
 COMPLIANCE WITH THE FOLLOW ITEMS:
  
 _X__ CONTRACTOR DID NOT PROVIDE THE MEAN
 ROOF HEIGHT.
  
 _X__ CONTRACTOR DID NOT INDICATE THE
 ROOF PITCH, OR THE DECK TYPE.
  
 _X__ CONTRACTOR FAILED TO INDICATE WHICH
 SYSTEM TO BE USED. THE SYSTEM SELECTED
 IS THE MEMBRANE UNDERLAYMENT FOR
 MECHANICALLY FASTENED TILE SYSTEM ONLY.
  
 2) FBC 1606.2.5.GENERAL LIMITATION
 #9 PROHIBITS RATIONAL ANALYSIS OR
 EXTRAPOLATION TO ENHANCE THE UPLIFT
 PRESSURE AT PERIMETER AND CORNER AREAS
 BY REDUCING THE FASTENER SPACING IN
 THESE AREAS.EITHER SELECT AN
 ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL)
 THAT DOES NOT CITE GENERAL LIMITATION
 #9.ALTERNATIVELY IF THE SELECTED
 SYSTEM DOES CITE GENERAL LIMITATION #9,
 IT MUST HAVE A MAXIMUM DESIGN PRESSURE
 THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3
 (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT
 OF 30 FEET OR LESS).
  
 3) PLEASE SEE THE ROOFING PROCEDURES
 POLICY ENCLOSE IN PACKAGE. ALL
 INFORMATION IS REQUIRED FOR PLAN REVIEW.
 ALSO TWO COPIES OF EACH PRODUCT APPROVAL
 IS REQUIRED. ONLY ONE STATE COVER SHEET
 WAS SUBMITTED.
  
 4) IS THIS A FLAT ROOF OR A PITCH ROOF
 PLEASE INDICATE ON THE APPLICATION ALONG
 WITH THE OTHER INFORMATION.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 TEL: (561) 805-6726
 FAX: (561) 659-8026


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved