Date |
Text |
2005-12-08 00:00:00 | |
| 1) THIS ROOF IS MISSING OR NOT IN |
| COMPLIANCE WITH THE FOLLOW ITEMS: |
| |
| _X__ CONTRACTOR DID NOT PROVIDE THE MEAN |
| ROOF HEIGHT. |
| |
| _X__ CONTRACTOR DID NOT INDICATE THE |
| ROOF PITCH, OR THE DECK TYPE. |
| |
| _X__ CONTRACTOR FAILED TO INDICATE WHICH |
| SYSTEM TO BE USED. THE SYSTEM SELECTED |
| IS THE MEMBRANE UNDERLAYMENT FOR |
| MECHANICALLY FASTENED TILE SYSTEM ONLY. |
| |
| 2) FBC 1606.2.5.GENERAL LIMITATION |
| #9 PROHIBITS RATIONAL ANALYSIS OR |
| EXTRAPOLATION TO ENHANCE THE UPLIFT |
| PRESSURE AT PERIMETER AND CORNER AREAS |
| BY REDUCING THE FASTENER SPACING IN |
| THESE AREAS.EITHER SELECT AN |
| ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL) |
| THAT DOES NOT CITE GENERAL LIMITATION |
| #9.ALTERNATIVELY IF THE SELECTED |
| SYSTEM DOES CITE GENERAL LIMITATION #9, |
| IT MUST HAVE A MAXIMUM DESIGN PRESSURE |
| THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3 |
| (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT |
| OF 30 FEET OR LESS). |
| |
| 3) PLEASE SEE THE ROOFING PROCEDURES |
| POLICY ENCLOSE IN PACKAGE. ALL |
| INFORMATION IS REQUIRED FOR PLAN REVIEW. |
| ALSO TWO COPIES OF EACH PRODUCT APPROVAL |
| IS REQUIRED. ONLY ONE STATE COVER SHEET |
| WAS SUBMITTED. |
| |
| 4) IS THIS A FLAT ROOF OR A PITCH ROOF |
| PLEASE INDICATE ON THE APPLICATION ALONG |
| WITH THE OTHER INFORMATION. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| TEL: (561) 805-6726 |
| FAX: (561) 659-8026 |