Plan Review Notes For Permit 05120078 |
Permit Number |
05120078 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-03-01 00:00:00 | *** UNSAT 3RD REVIEW *** | | | | ** PLEASE KNOW, NEW PLANS BY A NEW | | DESIGNER IS NOW BEING SUBMITTED FOR THE | | FIRST TIME. | | PLEASE SEE SOME NOTES BELOW AS SOME ARE | | NOW NEW AND SOME ARE FROM PREVIOUS | | REVIEW. | | | | 1)NOTE: PLEASE SEE LOAD CALCUALTIONS NOW | | SHOW TWO SETS OF "SHOW WINDOW" LIGHTING | | AT 6KW? , HOWEVER PLANS AND PANEL | | SCHEDULE CIRCUITING DOES NOT INDICATE | | ANY OF THIS? PLEASE SHOW FIXTURES ETC | | WHICH ARE BEING INSTALLED FOR THIS. | | 215.5 | | | | 2)NOTE: PLEASE SEE OCCUPANCY | | DESIGNATION/USE OF UNIT BLDG ETC IS | | STILL NOT BEING INDICATED ON PLANS AS | | REQUESTED ON THE PREVIOUS REVIEWS. | | ?? | | | | 3)NOTE: PLEASE SEE 700.12E FOR | | CIRCUTIING OF EM/EXT LTS. THESE MUST BE | | CIRCUITED TO THE LOCAL BRANCH CIRCUIT | | FEEDING ANY ONE AREA. | | | | 4)NOTE: PLEASE SEE FBC CHAPTER 13 | | 13-415.1.ABC.1.1 &.2 | | PLEASE KNOW,SQ FT OF BLSG IS NOT KNOWN | | AND IS NOT SHOWN ON PLANS. | | | | ** PLEASE SEE ANY OTHER COMMENTS FROM | | OTHER TRADE WHICH MAY AFFECT ELECTRICLA | | PLANS. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] | | |
|