2006-01-23 00:00:00 | *********** UNSAT 2ND REVIEW ******* |
| |
| |
| PLEASE SEE COMMENTS FROM PREVIOUS REVIEW |
| WHICH STILL NEED TO BE ADDRESSED. |
| |
| |
| 1)NOTE: PLEASE SUBMIT PLANS WITH |
| DRAFTMANS QUALITY. |
| FBCADMINISTRATIVE CODE 106 |
| |
| 2)NOTE: PLEASE SEE VALUATION HAS NOT |
| BEEN INCREASED AND VALUE SHALL BE |
| ACCESSED BY THIS OFFICE IF AN |
| APPROPRIATE VALUE IS ADJUSTED. |
| PLEASE SEE THE ELECTRICAL WORK ALONE IS |
| SUBSTANIAL. |
| FBC 108.3 |
| |
| 3)NOTE: PLEASE SEE ALL PLANS SHALL |
| CONTAIN THE PRINTED NAME AND SIGNATURE |
| OF THE PERSON RESPONSIBLE FOR SAID |
| PLANS/DESIGN. |
| |
| 4)NOTE: PLEASE SEE 700.12E FOR |
| CIRCUITING OF EXT AND EM LTS AS ON |
| PREVIOUS REVIEW. THESE SHALL BE |
| CIRCUITED TO THE LOCAL LIGHTING BRANCH |
| CIRCUIT. |
| PLEASE SEE EM LTS ON WITH RECEPTS. |
| |
| 5)NOTE: PLANS SHALL DESIGNATE OCCUPANCY |
| FOR USE. |
| |
| 6)NOTE: PLEASE SEE NOTE #6 FROM PREVIOUS |
| REVIEW ALSO. |
| |
| PLEASE SEE OTHER REVIEWERS COMMENTS. |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| 561-805-6717 |
| [email protected] |
| |
| NOTES FOR FIRST REVIEW. |
| |
| PLEASE SEE VALUATION FOR SCOPE OF WORK |
| IS LOW AND MSUT BE INCREASED TO AN |
| APPROPRIATE VALUE OR ONE SHALL BE |
| ASSESSED PER MARSHALL'S/ SWIFT GUIDE. |
| PLEASE KNOW, THE 4X FEE SHALL BE |
| ADJUSTED UPON VALUE INCREASE AND FEES |
| WILL BE DUE. |
| FBC ADMINISTRATIVE SECTION. 108.3 |
| |
| 2)NOTE: PLEASE SUBMIT PLANS WITH |
| DRAFTMANS QUALITY FOR ALL DETAILS AND |
| SCOPE OF WORK TO BE PERFORMED. |
| FBC 106 |
| |
| 3)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH A PANEL |
| SCHEDULE TO BE SUBMITTED. |
| PLEASE SHOW SIZE OF PANEL AND NEW AND |
| EXISTING LOADS. |
| 215.5 |
| PLEASE ALSO SEE 700.12E FOR CIRCUITING |
| OF EM/EXT LTS. (LOCAL LIGHTING BRNACH |
| CIRCUIT) |
| |
| 4)NOTE: OK. |
| |
| 5)NOTE: OK, SEE NEW NOTES |
| |
| 6)NOTE: PLEASE SEE PLANS SUBMITTED |
| MENTIONS: " ALL IMPROVEMENTS ARE |
| EXISTING. ADDITIONAL DRAWINGS WILL BE |
| SUBMITTED FOR THE REMAINDER OF PROPOSED |
| CONSTRUCTION"?? |
| PLEASE CLARIFY THIS. |
| |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |