Text |
2005-12-30 00:00:00 | ************ UNSAT ************* |
| |
| |
| 1)NOTE: PLEASE SEE PERMIT APPLICATION: |
| PLEASE BES URE CONTRACTOR SIGNS PERMIT |
| APPLICATION. MUST BE NOTORIZED IF |
| QUALIFIER DOES NOT BRING IN. |
| PLEASE SEE VALUATION FOR SCOPE OF WORK |
| IS LOW AND MSUT BE INCREASED TO AN |
| APPROPRIATE VALUE OR ONE SHALL BE |
| ASSESSED PER MARSHALL'S/ SWIFT GUIDE. |
| PLEASE KNOW, THE 4X FEE SHALL BE |
| ADJUSTED UPON VALUE INCREASE AND FEES |
| WILL BE DUE. |
| FBC ADMINISTRATIVE SECTION. 108.3 |
| |
| 2)NOTE: PLEASE SUBMIT PLANS WITH |
| DRAFTMANS QUALITY FOR ALL DETAILS AND |
| SCOPE OF WORK TO BE PERFORMED. |
| FBC 106 |
| |
| 3)NOTE: PLEASE SHOW ALL CIRCUITING ON |
| PLANS AND CORRELATE WITH A PANEL |
| SCHEDULE TO BE SUBMITTED. |
| PLEASE SHOW SIZE OF PANEL AND NEW AND |
| EXISTING LOADS. |
| 215.5 |
| PLEASE ALSO SEE 700.12E FOR CIRCUITING |
| OF EM/EXT LTS. (LOCAL LIGHTING BRNACH |
| CIRCUIT) |
| |
| 4)NOTE: PLEASE SEE NEW A/C BEING SHOWN, |
| HOWEVER NO INFORMATION SUBMITTED FOR |
| LOADS ETC. |
| |
| 5)NOTE: PLEASE SEE PLANS INDICATE A |
| "STORE"??, PLEASE INCLUDE STOREFRONT |
| WINDOWS, PER 210.62. |
| PLEASE SEE 600.5 FOR MISSING SIGN |
| CIRCUIT. |
| |
| 6)NOTE: PLEASE SEE PLANS SUBMITTED |
| MENTIONS: " ALL IMPROVEMENTS ARE |
| EXISTING. ADDITIONAL DRAWINGS WILL BE |
| SUBMITTED FOR THE REMAINDER OF PROPOSED |
| CONSTRUCTION"?? |
| PLEASE CLARIFY THIS. |
| |
| |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |