2006-05-08 00:00:00DENIED
  
 1. PRODUCT APPROVALS REQUIRED FOR
 EXTERIOR DOORS AND STRAPS AND TIEDOWNS.
  
 2. ALL PRODUCT APPROVALS SUBMITTED SHALL
 HAVE THE FOLLOWING STATE PRODUCT
 APPROVALS ATTACHED.
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 4. W P B ADMINISTRATIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 5.SHOW DETAILS FOR WALL FRAMING AND
 ROOF REPAIRS.
  
 7.A DESIGN PROFESSIONAL OR AN OWNER
 MUST ELECT ONE OR A COMBINATION OF
 LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303 , 304 AND 305 OF THIS CODE.
 2004 FLORIDA EXISTING BUILDING CODE.
  
 8. WPB AMMENDMENTS TO THE 2004 FBC
 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR
 BUILDINGS. THE EXAMINATION OF THE
 DOCUMENTS BY THE BUILDING OFFICIAL SHALL
 INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN;FLOOR/ROOF
 FRAMING PLAN OR TRUSS LAYOUT; AND ALL
 EXTERIOR ELEVATIONS.
 INSUFFICIENT INFORMATION PROVIDED FOR A
 COMPLETE PLAN REVIEW.ADDITIONAL
 COMMENTS MAY ARISE AFTER REVIEWING
 UPDATED PLANS.SCOPE OF WORK ON
 APPLICATION DOES NOT REFLECT WORK SHOWN
 ON PLANS.PLANS ALSO DO NOT SHOW
 COMPLETE SCOPE OF WORK TO BE COMPLETED.
  
 9. SELECT THE ROOF ASSEMBLY USED ON THE
 MIAMI-DADE PRODUCT APPROVAL SUBMITTED.
 WPB AMMENDMENTS TO THE 2004 FBC
 106.1.1.2 FOR ROOF ASSEMBLIES REQUIRED
 BY THE CODE, THE CONSTRUCTION DOCUMENTS
 SHALL ILLUSTRATE, DESCRIBE, AND
 DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS,
 FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO
 BE INSTALLED. PRODUCT EVALUATION AND
 INSTALLATION SHALL INDICATE COMPLIANCE
 WITH THE WIND WPB AMENDMENTS TO FBC 2004
 EDITION 1.10 CRITERIA REQUIRED FOR THE
 SPECIFIC SITE OR A STATEMENT BY AN
 ARCHITECT OR ENGINEER FOR THE SPECIFIC
 SITE MUST BE SUBMITTED WITH THE
 CONSTRUCTION DOCUMENTS.
  
 A.INCLUDE A DOOR AND WINDOW SCHEDULE.
  
 B.PERMIT VALUATION IS TOO LOW AND DOES
 NOT REFLECT ALL WORK SHOWN.ADDITIONAL
 PERMIT FEES WILL BE DUE.
  
 C.PLANS ARE VAGUE AND DO NOT SHOW
 COMPLETE SCOPE OF WORK TO BE COMPLETED.
  
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 ART LANGE
 BUILDING PLANS EXAMINER
 805-6672