Plan Review Notes
Plan Review Notes For Permit 05111207
Permit Number 05111207
Review Stop E
Sequence Number 9
Notes
Date Text
2008-03-04 15:55:57** DENIEDREVIEW **
  
 ** PLEASE SEE COMMENTS FROM THE PREVIOUS REVIEW ARE
 STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE NOTES FROM PREVIOUS REVIEW WHICH
 REQUESTED THE INPUT DATA REPORT ON THE ENERGY
 CALCULATIONS TO CORRELATE WITH PLANS.
 ** PLEASE SEE FOR EXAMPLE FIXTURE L2 AS THE IDR ONLY
 SHOWS ONE FIXTURE YET THE PLANS SHOWS SEVERAL MORE THAN
 THIS.
 PLEASE SEE 13-415.1.A, 13-400.3.A
 *2004 FBC 2.11 VERSION IS OK HOWEVER ALL LIGHTING ON
 PLANS NEEDS TO COORDINATE WITH THE CALCULATIONS.
 ** ENERGY CALCULATIONS BEING ROUTED TO MECHANICAL AND
 BUILDING REVIEWERS.
  
 2) NOTE: ENERGY CALCULATIONS ARE NOT SUBMITTALS. OWE
 REVISION FEE OF $60, RECEIPT ATTACHED.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]