2008-07-28 15:31:57REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P2.1.1 REVISIONS NOT CLOUDED BY MATCH LINE ALONG
 COLUUM LINE 10.--IDENTIFY NEW FIXTURES IN THE
 TOILET ROOM. THERE IS NO SANITARY SHOWN TO THESE
 FIXTURES. SECTION 106.1.3.
  
 2. SHT P2.1.2 MANY REVISIONS/CHANGES ARE NOT INDICATED
 WITH A CLOUD NOR REVISION NUMBER.--REVISION 15
 BETWEEN COLUUMS F-H/1-3 DOES NOT INDICATE
 CHANGE/REVISION FROM FILE SET OF PLANS. PLEASE
 CLARIFY.
  
 3. SHT P3.1.1 IDENTIFY NEW FIXTURES IN THE TOILET
 ROOMS.--NOT FIXTURES ARE SHOWN WHERE HDF/DF IS
 INDICATED. PLEASE SHOW ALL FIXTURES. SECTION 106.1.3.
  
 4. SHT P3.1.2 MANY REVISIONS NOT CLOUDED NOR INDICATED
 WITH A REVISION NUMBER. SECTION 106.1.3.
  
 5. SHT P5.1 MANY REVISIONS ARE NOT CLOUDED NOR
 INDICATED WITH A REVISION NUMBER. SECTION 106.1.3.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  