2008-07-02 11:07:15REVISIONS DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHTS P2.1.1, P2.1.2, P3.1.1, P3.1.3 & P5.1 SHOWS
 REVISION #15 ON THE FLOOR PLAN, BUT NO REVISION #15
 SHOWN ON THE REVISION INDEX IN THE TITLE BLOCK. PLEASE
 CORRELATE. SECTION 106.1.3.--ALSO TURN OFF THE
 CLOUDS AND REVISION NUMBERS ON THE FLOOR PLANS FROM
 PREVIOUSLY APPROVED REVISIONS TO HELP EXPEDITE THE PLAN
 REVIEW PROCESS.
  
 2. SHT P2.1.1 DRINKING FOUNTAINS SHALL NOT BE INSTALLED
 IN PUBLIC RESTROOMS PER SECTION 410.2.--WHERE MORE
 THAN ONE DRINKING FOUNTAIN IS PROVIDED ON A FLOOR, AT
 LEAST 50% OF THOSE PROVIDED SHALL COMPLY WITH SECTION
 11-4.15 AND BE ON AN ACCESSIBLE ROUTE. SECTION
 11-4.1(10)(B). PLEASE INDICATE ALL ACCESSIBLE DRINKING
 FOUNTAINS.
  
 3. SHT P2.1.2 THERE ARE CHANGES/REVISIONS ON THE PLANS
 THAT ARE NOT CLOUDED OR NUMBERED AS A REVISION. PLEASE
 CLOUD AND NUMBER ALL REVISIONS TO BE SUBMITTED. SECTION
 106.1.3.
  
 4. SHT P5.1 WATER ISOMETRIC. THE LAV RELOCATED IN THE
 ACCESSIBLE STALL STILL SHOWS THE HOT WATER SUPPLY TO
 LAV IN THE PREVIOUS LOCATION. PLEASE CLARIFY. SECTION
 601.1.
  
 5. SHT P5.1 WATER ISOMETRIC. THE SINK ADDED BEHIND THE
 SHOWER IS INDICATED AS A SHOWER FIXTURE, (SH-1). PLEASE
 CLAIRFY.--PLEASE NUMBER THE REVISION CLOUD FOR SAME
 FIXTURE. SECTION 106.1.1.
  
 6. SHT P5.1 WATER ISOMETRIC. THE SUPPLY LINE TO THE 3
 LAVS IN THE WOMEN'S TOILET ROOM SHOWS NO CONNECTION TO
 THE WATER MAIN IN THE CEILING. PLEASE SHOW WHERE THE
 SUPPLY LINE CONNECTS TO WATER MAIN, (2"). SECTIONS
 106.1.1 & 601.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved