Plan Review Notes For Permit 05111207 |
Permit Number |
05111207 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-11-22 14:34:12 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | | | 1. SHT GO.O CODE ANALYSIS, FIXTURE COUNT INDICATES 5 | | DRINKING FOUNTAINS PROVIDED. ONLY 3 DRINKING FOUNTAINS | | ARE LOCATED. PLEASE CLARIFY. 2 SERVICE SINKS ARE | | INDICATED AS BEING PROVIDED. ONLY 1 SERVICE SINK IS | | LOCATED. PLEASE CLARIFY. TABLES 1004.1.2 & TABLE | | 403.1. | | | | 2. SHT P5.1 DOMESTIC WATER ISOMETRIC. THE TWO WATER | | CLOSETS AND ACCESSIBLE LAV FOR THE MEN'S TOILET ROOM, | | (102), ARE NOT INDICATED ON THE WATER RISER DIAGRAM. | | PLEASE CORRELATE THE RISER WITH THE FLOOR PLAN. SECTION | | 106.1.1. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] | | |
|