Plan Review Notes
Plan Review Notes For Permit 05111207
Permit Number 05111207
Review Stop P
Sequence Number 3
Notes
Date Text
2006-11-22 14:34:12DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT GO.O CODE ANALYSIS, FIXTURE COUNT INDICATES 5
 DRINKING FOUNTAINS PROVIDED. ONLY 3 DRINKING FOUNTAINS
 ARE LOCATED. PLEASE CLARIFY. 2 SERVICE SINKS ARE
 INDICATED AS BEING PROVIDED. ONLY 1 SERVICE SINK IS
 LOCATED. PLEASE CLARIFY. TABLES 1004.1.2 & TABLE
 403.1.
  
 2. SHT P5.1 DOMESTIC WATER ISOMETRIC. THE TWO WATER
 CLOSETS AND ACCESSIBLE LAV FOR THE MEN'S TOILET ROOM,
 (102), ARE NOT INDICATED ON THE WATER RISER DIAGRAM.
 PLEASE CORRELATE THE RISER WITH THE FLOOR PLAN. SECTION
 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved