Plan Review Notes
Plan Review Notes For Permit 05111207
Permit Number 05111207
Review Stop E
Sequence Number 3
Notes
Date Text
2006-10-26 20:07:35*** UNSAT 3RD REVIEW ***
  
 1) NOTE: PLEASE SEE PLANS AS THERE ARE AREAS WHERE
 LIGHTING OVER RIDE CONTROLS ARE MISSING. PLEASE SEE
 AREAS NOT NOTED IS DEVICE NOT SHOWN AS "S OC" ETC.
 PLEASE SEE SOME OF THESE ARE RED-LINED, BATH RM, MEN'S/
 WOMEN'S(TWO SETS) SEC'S OFFICE, PARTS, PARTS
 RECEIVING,, OFFICE BATH, STORAGE ETC.
 PLEASE SEE 13-415.1.AB.1, WHICH SPEAKS OF TABLES IN
 415.2.
 PLEASE SEE PERFORMANCE CALCULATIONS WERE NOT LOCATED IN
 SETS. SHEET 7.1 MENTIONS TO SEE ENERGY CALCULATIONS,
 HOWEVER PLEASE SEE 13-415.2.ABC.1. PLEASE SEE CODE
 WHICH SPEAKS OF CERTAIN TRADES OFF NOT PERMITTED.
 PLEASE SEE LIGHTING LEVELS SHALL BE PER TABLE SIN
 415.2.C.1, OR 415.2.B.1. ASPLANS APPEAR TO BE MORE OF
 A SPACE BY SPACE, THIS MAY BE DONE ON PLANS ON A
 "TABLE" OF SORTS INDICATING THE AREAS ,PERMITTED LPD
 PER SQ FT. PLEASE SEE THE LEVELS AS SHOWN ON 7.1 DO NOT
 APPEAR TO CORRELATE MAX PERMITTED IN THE TABLES.
 PLEASE SEE SOME AREAS CAN BE DONE PER 13-415.2.B.2
  
 PLEASE SEE METHOD "A" SHOWS ALL MANUAL ? ON/OFF?
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  