Notes |
Date |
Text |
2006-07-15 00:00:00 | PAUL SCHMITZ | | [email protected] | | FBC 2004 PLUMBING CODE PLAN REVIEW | | FBC2004 FUEL GAS CODEPLAN REVIEW | | FBC 2004 CH 11, FL ACESSIBILITY CODE | | AMENDMENTS TO THE FLORIDA BUILDING CODE | | CHAPT.1, ADMINISTRATION, 2004 EDITION | | | | UNSAT | | PREVIOUS COMMENT DATED 3-4-06 #8 | | | | NO DOORS ON BASE OF CABNET. | | | | | | 8. BREAK ROOM SINK SHALL COMPLY WITH | | 11-4.24 AND ALL SUBSECTIONS. | | SUBMIT A DETAIL SHOWING COMPLIANCE. | | A. 11-4.24.2 HEIGHT | | B. 11-4.24.3 KNEE CLEARANCE | | D. 11-4.24.5 CLEAR FLOOR SPACE | | | | (FORWARD APPROACH, EXTENDING A MAXIMUM | | OF 19" UNDERNEATH THE SINK REQUIRED). | | | | E. 11-4.24.6 EXPOSED PIPES AND SURFACES | | | | END OF COMMENTS, QUESTIONS 561-805-6692 |
|