2006-06-25 00:00:00 | IN ELEC |
| *** UNSAT 2ND REVIEW *** |
| |
| 1) NOTE: PLEASE SEE NOTE #1 FROM |
| PREVIOUS REVIEW AS PLANS PREVIOUSLY CAME |
| IN UNDER THE 2001 DESIGN. IT WAS |
| REQUESTED TO SEE 2004 FBC FOR DESIGN AS |
| THE CODE HAD CHANGED ON OCT 1ST, 2005 TO |
| THE NEW CODE. |
| PLEASE SEE HAVE NOW COME BACK AND |
| RESPONSE MENTIONS ALL DESIGNS ARE NOW |
| UNDER THE 2004 FBC. |
| PLEASE SEE FBC CHAPTER 13 REQUIREMENTS |
| COULD NOT BE LOCATED IN DESIGN/OR ON |
| PLANS. |
| PLEASE PROVIDE WORST CASE VOLTAGE DROP |
| PER 13-413.1ABC.1 |
| PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND |
| .1.3 FOR LIGHTING CONTROLS REQUIRED. |
| PLEASE INDICATE THE NEW SYSTEM BEING |
| USED, SCHEDULING, OVER-RIDES DEVICES, |
| LOCATIONS, AND THE TIMES OF OVER-RIDES |
| DEVICES, DEPENDING ON INSTALLATION AND |
| TYPE OF DEVICES INSTALLED. |
| PLEASE SEE13-415.1.ABC.3, |
| PLEASE SEE 13-415.1.AB.1 FOR MIN |
| CALCULATIONS FOR LIGHTING LEVELS AND |
| DENSITIES (LPD)TO BE PROVIDED. |
| PLEASE SEE 13-415.2.ABC.1, AND SPECIFY |
| METHOD AND TABLES. (415.2.C.1,415.2.B.1 |
| |
| ** THE FOLLWING IS NOT A KAMM CONSULTING |
| ENG'S COMMENT. |
| |
| 2) NOTE: PLEASE SEE LANDSCAPE PLANS AS |
| THE FIRM "KILDAY AND ASSOCIATES" IS |
| MISSING THE REQUIRED INFORMATION ON |
| TITLE BLOCKS AS SET-FORTH IN THE FAC |
| 61G1-16.004 |
| PLEASE SEE MISSING THE PRINTED NAME AND |
| LICENSE NUMBER OF THE LANDSCAPE ARCH. |
| PLEASE SEE MISSING CERTIFICATE OF |
| AUTHORIZATION NUMBER AS REQUIRED PER FS |
| 481.319. |
| |
| 3) NOTE: PLEASE SEE THE RECORDED NOTICE |
| OF COMMENCMENT SUBMITTED HAS EXPIRED PER |
| FS 713.13(2). PLEASE KNOW, IF WORK HAS |
| NOT COMMENCED WITH IN 90 DAYS OF |
| RECORDING NOC, THEN THE NOC WILL BECOME |
| "VOID" AND WILL BE REQUIRED TO BE RE- |
| RECORDED. PLEASE KNOW, THE NOC IS ONLY |
| REQUIRED BEFORE PICKING UP PERMIT. |
| |
| 4) NOTE: PLEASE BE SURE TO "COMPLETELY |
| REMOVE" ALL OLD/VOIDED SHEETS AND ONLY |
| INSERT NEW REVISED SHEETS INTO COMPLETE |
| SETS FOR REVIEW AND STAMPING. PLEASE |
| ONLY SUBMIT ONE COPY OF THE OLD/VOIDED |
| REMOVED SHEETS SEPARATELY FOR REFERENCE. |
| |
| |
| ** PLEASE SEE ANY COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |