Plan Review Notes
Plan Review Notes For Permit 05111207
Permit Number 05111207
Review Stop E
Sequence Number 2
Notes
Date Text
2006-06-25 00:00:00IN ELEC
 *** UNSAT 2ND REVIEW ***
  
 1) NOTE: PLEASE SEE NOTE #1 FROM
 PREVIOUS REVIEW AS PLANS PREVIOUSLY CAME
 IN UNDER THE 2001 DESIGN. IT WAS
 REQUESTED TO SEE 2004 FBC FOR DESIGN AS
 THE CODE HAD CHANGED ON OCT 1ST, 2005 TO
 THE NEW CODE.
 PLEASE SEE HAVE NOW COME BACK AND
 RESPONSE MENTIONS ALL DESIGNS ARE NOW
 UNDER THE 2004 FBC.
 PLEASE SEE FBC CHAPTER 13 REQUIREMENTS
 COULD NOT BE LOCATED IN DESIGN/OR ON
 PLANS.
 PLEASE PROVIDE WORST CASE VOLTAGE DROP
 PER 13-413.1ABC.1
 PLEASE SEE 13-415.1.ABC.1.1, .1.2 AND
 .1.3 FOR LIGHTING CONTROLS REQUIRED.
 PLEASE INDICATE THE NEW SYSTEM BEING
 USED, SCHEDULING, OVER-RIDES DEVICES,
 LOCATIONS, AND THE TIMES OF OVER-RIDES
 DEVICES, DEPENDING ON INSTALLATION AND
 TYPE OF DEVICES INSTALLED.
 PLEASE SEE13-415.1.ABC.3,
 PLEASE SEE 13-415.1.AB.1 FOR MIN
 CALCULATIONS FOR LIGHTING LEVELS AND
 DENSITIES (LPD)TO BE PROVIDED.
 PLEASE SEE 13-415.2.ABC.1, AND SPECIFY
 METHOD AND TABLES. (415.2.C.1,415.2.B.1
  
 ** THE FOLLWING IS NOT A KAMM CONSULTING
 ENG'S COMMENT.
  
 2) NOTE: PLEASE SEE LANDSCAPE PLANS AS
 THE FIRM "KILDAY AND ASSOCIATES" IS
 MISSING THE REQUIRED INFORMATION ON
 TITLE BLOCKS AS SET-FORTH IN THE FAC
 61G1-16.004
 PLEASE SEE MISSING THE PRINTED NAME AND
 LICENSE NUMBER OF THE LANDSCAPE ARCH.
 PLEASE SEE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER AS REQUIRED PER FS
 481.319.
  
 3) NOTE: PLEASE SEE THE RECORDED NOTICE
 OF COMMENCMENT SUBMITTED HAS EXPIRED PER
 FS 713.13(2). PLEASE KNOW, IF WORK HAS
 NOT COMMENCED WITH IN 90 DAYS OF
 RECORDING NOC, THEN THE NOC WILL BECOME
 "VOID" AND WILL BE REQUIRED TO BE RE-
 RECORDED. PLEASE KNOW, THE NOC IS ONLY
 REQUIRED BEFORE PICKING UP PERMIT.
  
 4) NOTE: PLEASE BE SURE TO "COMPLETELY
 REMOVE" ALL OLD/VOIDED SHEETS AND ONLY
 INSERT NEW REVISED SHEETS INTO COMPLETE
 SETS FOR REVIEW AND STAMPING. PLEASE
 ONLY SUBMIT ONE COPY OF THE OLD/VOIDED
 REMOVED SHEETS SEPARATELY FOR REFERENCE.
  
  
 ** PLEASE SEE ANY COMMENTS FROM OTHER
 TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  