Date |
Text |
2006-07-18 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| FROM PREVIOUS REVIEW |
| |
| 19.)PRODUCT APPROVALS REQUIRED FOR ALL |
| COMPONENTS AND CLADDING, INCLUDING THE |
| EIFS SYSTEM, FAC9B72.FLORIDA STATE OR |
| LOCAL PRODUCT APPROVALS REQUIRED, |
| FAC9B72.WWW.FLORIDABUILDING.ORG |
| PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| DESIGNER OF RECORD, FBC*106.3.3. |
| |
| THE REVIEW MAY BE DONE IN THE FORM OF A |
| SHOP DRAWING STAMP.THE STATE PRODUCT |
| APPROVAL IS NOT REQUIRED TO BE ON THE |
| PLAN. |
| |
| A CURRENT FLORIDA STATE OR LOCAL PRODUCT |
| APPROVAL IS REQUIRED, FAC9B72.IF A |
| FLORIDA STATE PRODUCT APPROVAL FOR 2004 |
| CODE IS NOT AVAILABLE FOR ANY OF THE |
| PRODUCTS, PLEASE ADVISE AND THE NOA WILL |
| BE REVIEWED FOR CODE COMPLIANCE AND IF |
| FOUND COMPLIANT, A LOCAL PRODUCT |
| APPROVAL WILL BE ISSUED. |
| |
| THE PLAN REFERS TO FL337.8 FOR THE |
| OVERHEAD DOOR, BUT THE PRODUCT APPROVAL |
| SUBMITTED WAS 742. |
| |
| THE STANLEY SLIDING DOOR IS NOT APPROVED |
| WHERE WATER INFILTRATION REQUIREMENTS |
| ARE NEEDED.THIS IS NOT A CODE |
| CORRECTION; PLEASE CONFIRM PRODUCT'S |
| CONFORMITY WITH DESIGN INTENT. |
| |
| PRODUCT APPROVALS WERE NOT SUBMITTED FOR |
| THE METAL DOORS SHOWN ON THE ELEVATIONS. |
| |
| AS DISCUSSED ON THE TELEPHONE, |
| REFERENCES TO SPECIFIC PRODUCTS ON THE |
| PLAN MAY BE ELIMINATED BY THE ARCHITECT |
| (INITIALED AND DATED) RATHER THAN |
| PRINTING NEW SHEETS. |
| |
| 22.)ID11.9, THE BREAK ROOM SINK IS TO |
| BE ACCESSIBLE, FBC11-4.24.THE CABINET |
| DOORS DO NOT ALLOW THE REQUIRED KNEE |
| CLEARANCE. |
| |
| NEW COMMENTS: |
| |
| 28.)THE ENGINEER'S SEAL IS EXPIRED |
| (SOILS REPORT).IT IS THE WRONG SIZE |
| AND SAYS "CERTIFICATE" RATHER THAN |
| "LICENSE".FAC61G15-23. |
| |
| 29.) PLEASE PROVIDE THE AREA INCREASE |
| CALCULATIONS ON THE PLAN FOR ALLOWABLE |
| AREA, SHEET G0.0. |
| |
| 30.)CLOUD ALL CHANGES.WHEN |
| RESUBMITTING, SUBMIT OLD SHEETS |
| SEPARATELY FOR REFERENCE. |
| |
| 31.)ADJACENT ACCESSIBLE PARKING IS TO |
| BE DISPERSED ACCORDING TO 11-4.6.2 (EXIT |
| 12). |
| |
| 32.)SEE ATTACHED FS553.A 4X PLAN |
| REVIEW IS REQUIRED TO BE CHARGED IF THE |
| COMMENTS ARE NOT ADDRESSED A THIRD TIME. |