Plan Review Notes
Plan Review Notes For Permit 05111207
Permit Number 05111207
Review Stop B
Sequence Number 2
Notes
Date Text
2006-07-18 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS REVIEW
  
 19.)PRODUCT APPROVALS REQUIRED FOR ALL
 COMPONENTS AND CLADDING, INCLUDING THE
 EIFS SYSTEM, FAC9B72.FLORIDA STATE OR
 LOCAL PRODUCT APPROVALS REQUIRED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
 PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD, FBC*106.3.3.
  
 THE REVIEW MAY BE DONE IN THE FORM OF A
 SHOP DRAWING STAMP.THE STATE PRODUCT
 APPROVAL IS NOT REQUIRED TO BE ON THE
 PLAN.
  
 A CURRENT FLORIDA STATE OR LOCAL PRODUCT
 APPROVAL IS REQUIRED, FAC9B72.IF A
 FLORIDA STATE PRODUCT APPROVAL FOR 2004
 CODE IS NOT AVAILABLE FOR ANY OF THE
 PRODUCTS, PLEASE ADVISE AND THE NOA WILL
 BE REVIEWED FOR CODE COMPLIANCE AND IF
 FOUND COMPLIANT, A LOCAL PRODUCT
 APPROVAL WILL BE ISSUED.
  
 THE PLAN REFERS TO FL337.8 FOR THE
 OVERHEAD DOOR, BUT THE PRODUCT APPROVAL
 SUBMITTED WAS 742.
  
 THE STANLEY SLIDING DOOR IS NOT APPROVED
 WHERE WATER INFILTRATION REQUIREMENTS
 ARE NEEDED.THIS IS NOT A CODE
 CORRECTION; PLEASE CONFIRM PRODUCT'S
 CONFORMITY WITH DESIGN INTENT.
  
 PRODUCT APPROVALS WERE NOT SUBMITTED FOR
 THE METAL DOORS SHOWN ON THE ELEVATIONS.
  
 AS DISCUSSED ON THE TELEPHONE,
 REFERENCES TO SPECIFIC PRODUCTS ON THE
 PLAN MAY BE ELIMINATED BY THE ARCHITECT
 (INITIALED AND DATED) RATHER THAN
 PRINTING NEW SHEETS.
  
 22.)ID11.9, THE BREAK ROOM SINK IS TO
 BE ACCESSIBLE, FBC11-4.24.THE CABINET
 DOORS DO NOT ALLOW THE REQUIRED KNEE
 CLEARANCE.
  
 NEW COMMENTS:
  
 28.)THE ENGINEER'S SEAL IS EXPIRED
 (SOILS REPORT).IT IS THE WRONG SIZE
 AND SAYS "CERTIFICATE" RATHER THAN
 "LICENSE".FAC61G15-23.
  
 29.) PLEASE PROVIDE THE AREA INCREASE
 CALCULATIONS ON THE PLAN FOR ALLOWABLE
 AREA, SHEET G0.0.
  
 30.)CLOUD ALL CHANGES.WHEN
 RESUBMITTING, SUBMIT OLD SHEETS
 SEPARATELY FOR REFERENCE.
  
 31.)ADJACENT ACCESSIBLE PARKING IS TO
 BE DISPERSED ACCORDING TO 11-4.6.2 (EXIT
 12).
  
 32.)SEE ATTACHED FS553.A 4X PLAN
 REVIEW IS REQUIRED TO BE CHARGED IF THE
 COMMENTS ARE NOT ADDRESSED A THIRD TIME.