Plan Review Notes
Plan Review Notes For Permit 05111207
Permit Number 05111207
Review Stop B
Sequence Number 16
Notes
Date Text
2009-03-04 11:16:27***PENDING REVISED VALUE***
 VALUE RECEIVED BY CONTRACTOR 3/12/9, ADJUSTED FEES
  
  
 ***REVISION SUBMITTED 1/21/09****
 ***PARTIAL REVIEW, SHEETS 0.0, A2.0A, A2.0B,
 A2.1A,A2.1B,A2.2A,A2.2B,A2
 .3,A2.5A,A2.5B,A2.6A,A2.6B,A2.7,A3.2,A4.3,A5.1,A7.0,A7.
 1,A14.2,A8.1,A8.3,ID9.1A,ID9.1B,ID9.2A,ID9.2B,ID9.3,ID1
 0.1,ID10.3,ID11.6A,S2.5,S3.8
 ***PASSED W/PROVISO***
  
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 ****PROVISOS****
  
 1. NO DOOR PERMITTED AT SALES 101B. REVISE SHEET TO
 REMOVE DOOR.
  
 2. DOOR 154 INDICATED AT OFFICE 101A; THIS DOOR DOES
 NOT FIT IN THIS LOCATION. PLEASE CORRELATE.
  
 3. DISTANCE BETWEEN COLUMN AND RETAIL PARTS ROOM 123
 COUNTER IS 3'6" PER ARCHITECT (FBC11-4.2.4.1).
  
 4. SUBJECT TO PLUMBING & ELECTRIC REVIEWS.
  
 5. REVISED ENERGY CALCS REQUIRED PRIOR TO CERTIFICATE
 OF COMPLETION.
  