Plan Review Notes
Plan Review Notes For Permit 05111207
Permit Number 05111207
Review Stop E
Sequence Number 13
Notes
Date Text
2008-12-08 09:11:36** DENIED REVIEW OF REVISIONS **
  
  
  
  
 1) NOTE: PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR
 ALL REVISED WORK AND SYSTEM. RESPONSE LETTER TO
 PREVIOUS REVISIONS WHICH HAD COMMENTS STATES SEE NEW
 PAGE E6.2 HOWEVER NO E6.2 IS IN ANY OF THE THREE SETS
 SUBMITTED.
 IN ORDER TO REVIEW CIRCUITING FOR NEW ITEMS ALONG WITH
 LOADS, PANEL, ETC PLEASE SUBMIT. THIS AFFECTS THE
 ENTIRE SET OF PLANS.
 240.4,310.16,408.4, 408.36 ETC
 FBC 106.1.1 FOR CLARITY, COORDINATION OF RECORD PLANS.
 THIS ADDITION OF THIS NEW PANEL WAS NOT ON PREVIOUS
 REVISIONS SUBMITTED.
  
 2) NOTE: PLEASE BE SURE THE LOADS ON RISER SHEET E5.1
 FOR MAIN #2 COORDINATE WITH THE DPA SCHEDULE ON E6.1.
 220.
 FBC 106.1.1
  
 3) NOTE: ENERGY CALCULATIONS NOT STAMPED AT THIS TIME.
 THERE ARE OPEN PERMITS WITH NEW LIGHTING ON THE
 EXTERIOR OF BUILDING AND PARKING AREAS WHICH ARE FED
 FROM THIS ELECTRICAL SERVICE WHICH IS NOW NEW. THE
 RISER COTNAINS SEVERAL SUB PANELS FOR EXTERIOR SITE
 LIGHTING YET NONE ARE LOCATED IN THE INPUT DATA REPORT.
 PLEASE BE SURE THE CALCULATIONS ARE REVISED
 ACCORDINGLY.
 13-415.2,13-415.2.ABC.1.3, 13-400.3.A
 ** PLEASE ALSO KNOW THERE ARE OTHER ITEMS ON THE IDR
 WHICH ARE BLANK FOR COMPONENTS WHICH ARE REQUIRED TO BE
 PART OF THE *WHOLE BUILDING METHOD*.
 PLEASE LOOK FOR COMMENTS FROM OTHER TRADES ON REVIEW OF
 CALCULATIONS.
 ** ONE EXAMPLE OF OTHER SYSTEMS IS THE IDR DO NOT
 INDICATE ANY FLOORS? THERE ARE OTHERS.
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  