2008-12-08 09:11:36 | ** DENIED REVIEW OF REVISIONS ** |
| |
| |
| |
| |
| 1) NOTE: PLEASE SUBMIT COMPLETE ELECTRICAL PLANS FOR |
| ALL REVISED WORK AND SYSTEM. RESPONSE LETTER TO |
| PREVIOUS REVISIONS WHICH HAD COMMENTS STATES SEE NEW |
| PAGE E6.2 HOWEVER NO E6.2 IS IN ANY OF THE THREE SETS |
| SUBMITTED. |
| IN ORDER TO REVIEW CIRCUITING FOR NEW ITEMS ALONG WITH |
| LOADS, PANEL, ETC PLEASE SUBMIT. THIS AFFECTS THE |
| ENTIRE SET OF PLANS. |
| 240.4,310.16,408.4, 408.36 ETC |
| FBC 106.1.1 FOR CLARITY, COORDINATION OF RECORD PLANS. |
| THIS ADDITION OF THIS NEW PANEL WAS NOT ON PREVIOUS |
| REVISIONS SUBMITTED. |
| |
| 2) NOTE: PLEASE BE SURE THE LOADS ON RISER SHEET E5.1 |
| FOR MAIN #2 COORDINATE WITH THE DPA SCHEDULE ON E6.1. |
| 220. |
| FBC 106.1.1 |
| |
| 3) NOTE: ENERGY CALCULATIONS NOT STAMPED AT THIS TIME. |
| THERE ARE OPEN PERMITS WITH NEW LIGHTING ON THE |
| EXTERIOR OF BUILDING AND PARKING AREAS WHICH ARE FED |
| FROM THIS ELECTRICAL SERVICE WHICH IS NOW NEW. THE |
| RISER COTNAINS SEVERAL SUB PANELS FOR EXTERIOR SITE |
| LIGHTING YET NONE ARE LOCATED IN THE INPUT DATA REPORT. |
| PLEASE BE SURE THE CALCULATIONS ARE REVISED |
| ACCORDINGLY. |
| 13-415.2,13-415.2.ABC.1.3, 13-400.3.A |
| ** PLEASE ALSO KNOW THERE ARE OTHER ITEMS ON THE IDR |
| WHICH ARE BLANK FOR COMPONENTS WHICH ARE REQUIRED TO BE |
| PART OF THE *WHOLE BUILDING METHOD*. |
| PLEASE LOOK FOR COMMENTS FROM OTHER TRADES ON REVIEW OF |
| CALCULATIONS. |
| ** ONE EXAMPLE OF OTHER SYSTEMS IS THE IDR DO NOT |
| INDICATE ANY FLOORS? THERE ARE OTHERS. |
| |
| |
| |
| |
| **IMPORTANT** |
| ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED |
| INTO TWO SETS/FOLDERS/BINDERS ETC. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| ANY DELAYS. |
| |
| IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO |
| CONTACT THIS REVIEWER. |
| |