2009-03-11 13:43:41 | DENIED |
| REFERENCE: |
| FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| A. NOTE: AS INDICATED PREVIOUSLY, TURN OFF ALL |
| PREVIOUSLY APPROVED REVISION CLOUDS AND REVISION |
| NUMBERS. THIS ADDS MUCH TIME TO THE REVIEW PROCESS AND |
| CONFUSES THE REVIEW PROCESS AS SOME NEW REVISIONS ARE |
| NOT APPARENT AND SOME REVISIONS SHOW A CLOUD AND A |
| REVISIONS NUMBER BUT NO APPARENT REVISION IS SHOWN. |
| ONLY SHOW THE NEW REVISION CLOUDS AND REVISIONS NUMBERS |
| FOR REVISIONS BEING CHANGED ON THIS SUBMITTAL. PLEASE |
| TURN OFF ALL PREVIOUS REVISIONS. SECTION 106.1.3. |
| |
| 1. SHT P2.1.1 SHOWS 4 DRINKING FOUNTAINS, BUT ONLY ONE |
| ACCESSIBLE DRINKING FOUNTAIN. PER SECTION 11-4.1(10)(B) |
| 50% OF ALL PROVIDED DRINKING FOUNTAINS SHALL BE |
| ACCESSIBLE. PLEASE INDICATE THE TWO REQUIRED DRINKING |
| FOUNTAINS. |
| |
| 2. SHT P2.1.1 REVISION 16B WAS NOT FOUND ON THE FLOOR |
| PLAN. PLEASE CORRELATE. -- THE PIPING TO THE 3 LAVS IN |
| THE WOMENS TOILET ROOM HAS BEEN REVISED WITH NO CLOUD |
| OR REVISION NUMBER. PLEASE SHOW CLOUDS AND REVISION |
| NUMBERS FOR ALL REVISIONS SUBMITTED. SECTION 106.1.3. |
| |
| 3. SHT P2.1.2 PLANS ARE NOT LEGIBLE BETWEEN COL. LINES |
| 10-11/F-O. ALSO MANY REVISION NUMBER 16'S SHOWN ON THE |
| FLOOR PLAN ARE NOT INDICATED IN THE REVISION INDEX. |
| SOME REVISIONS 16B & 17 SHOW NO CHANGES TO THE |
| PLUMBING. PLEASE CLARIFY. SECTIONS 106.1.2 & 106.1.3. |
| |
| 4. SHT P3.1.1 SHOWS 2 REVISION NUMBER 5 THAT WERE NOT |
| ON PREVIOUS REVISION SHEET SIGNED, SEALED ON JULY 28, |
| 2008. IF THESE ARE NEW REVISION THEN NEW REVISION |
| NUMBERS ARE REQUIRED. SECTION 106.1.3. -- REVISION |
| NUMBER 17 AT ROOM 104 SHOWS NO PLUMBING REVISION. |
| PLEASE CLARIFY. SECTION 106.1.1. |
| |
| 5. SHT P3.1.2 NO CHANGES WERE FOUND WITHIN THE CLOUDS |
| FOR REVISIONS 16/16B/17. PLEASE CLARIFY. SECTIONS |
| 106.1.1 & 106.1.3. |
| |
| 6. SHT P5.1 MANY REVISION NUMBERS SHOW NO |
| CHANGE/REVISION TO THE PLANS WITHIN THE CLOUDED AREA. |
| PLEASE CLARIFY WHAT IS REVISED IN EACH CLOUDED AREA. |
| SECTION 106.1.1. REVISION 17 SHOWS A CAPPED HUB DRAIN. |
| PER SECTION 704.5 DEAD ENDS ARE PROHIBITED. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| WITH A DESCRIPTION OF THE REVISION MADE, |
| IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| ONE SET OF THEM LOOSELY ON TOP OF THE |
| COLLATED PLANS TO BE REVIEWED. |
| THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |