Plan Review Notes
Plan Review Notes For Permit 05111207
Permit Number 05111207
Review Stop P
Sequence Number 12
Notes
Date Text
2009-03-11 13:43:41DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 A. NOTE: AS INDICATED PREVIOUSLY, TURN OFF ALL
 PREVIOUSLY APPROVED REVISION CLOUDS AND REVISION
 NUMBERS. THIS ADDS MUCH TIME TO THE REVIEW PROCESS AND
 CONFUSES THE REVIEW PROCESS AS SOME NEW REVISIONS ARE
 NOT APPARENT AND SOME REVISIONS SHOW A CLOUD AND A
 REVISIONS NUMBER BUT NO APPARENT REVISION IS SHOWN.
 ONLY SHOW THE NEW REVISION CLOUDS AND REVISIONS NUMBERS
 FOR REVISIONS BEING CHANGED ON THIS SUBMITTAL. PLEASE
 TURN OFF ALL PREVIOUS REVISIONS. SECTION 106.1.3.
  
 1. SHT P2.1.1 SHOWS 4 DRINKING FOUNTAINS, BUT ONLY ONE
 ACCESSIBLE DRINKING FOUNTAIN. PER SECTION 11-4.1(10)(B)
 50% OF ALL PROVIDED DRINKING FOUNTAINS SHALL BE
 ACCESSIBLE. PLEASE INDICATE THE TWO REQUIRED DRINKING
 FOUNTAINS.
  
 2. SHT P2.1.1 REVISION 16B WAS NOT FOUND ON THE FLOOR
 PLAN. PLEASE CORRELATE. -- THE PIPING TO THE 3 LAVS IN
 THE WOMENS TOILET ROOM HAS BEEN REVISED WITH NO CLOUD
 OR REVISION NUMBER. PLEASE SHOW CLOUDS AND REVISION
 NUMBERS FOR ALL REVISIONS SUBMITTED. SECTION 106.1.3.
  
 3. SHT P2.1.2 PLANS ARE NOT LEGIBLE BETWEEN COL. LINES
 10-11/F-O. ALSO MANY REVISION NUMBER 16'S SHOWN ON THE
 FLOOR PLAN ARE NOT INDICATED IN THE REVISION INDEX.
 SOME REVISIONS 16B & 17 SHOW NO CHANGES TO THE
 PLUMBING. PLEASE CLARIFY. SECTIONS 106.1.2 & 106.1.3.
  
 4. SHT P3.1.1 SHOWS 2 REVISION NUMBER 5 THAT WERE NOT
 ON PREVIOUS REVISION SHEET SIGNED, SEALED ON JULY 28,
 2008. IF THESE ARE NEW REVISION THEN NEW REVISION
 NUMBERS ARE REQUIRED. SECTION 106.1.3. -- REVISION
 NUMBER 17 AT ROOM 104 SHOWS NO PLUMBING REVISION.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 5. SHT P3.1.2 NO CHANGES WERE FOUND WITHIN THE CLOUDS
 FOR REVISIONS 16/16B/17. PLEASE CLARIFY. SECTIONS
 106.1.1 & 106.1.3.
  
 6. SHT P5.1 MANY REVISION NUMBERS SHOW NO
 CHANGE/REVISION TO THE PLANS WITHIN THE CLOUDED AREA.
 PLEASE CLARIFY WHAT IS REVISED IN EACH CLOUDED AREA.
 SECTION 106.1.1. REVISION 17 SHOWS A CAPPED HUB DRAIN.
 PER SECTION 704.5 DEAD ENDS ARE PROHIBITED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  