2008-08-15 10:49:12 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| |
| 1.PLEASE NOTE THAT, IN THE LAST REVISION, ONLY |
| CHANGES CLOUDED WERE REVIEWED.SOME OF REVISION 15 |
| WERE INCLUDED IN REVISION 14 BUT NOT CLOUDED. THEREFORE |
| SOME OF THE CHANGES WHICH WERE INADVERTENTLY PASSED |
| UNDER REVISION 14 WERE NEVER REVIEWED AND MAY HAVE |
| COMMENTS IN THIS REVIEW. |
| |
| PLEASE HAVE THE DESIGNER REVIEW THE PLANS AND CONFIRM |
| THAT ALL CHANGES (FROM THE ISSUED PERMIT SET) ARE |
| CLOUDED. |
| |
| 2.PLEASE CLARIFY ALLOWABLE BUILDING AREA AND |
| PROPOSED; SHEET G0.0 STATES THAT ALLOWABLE BUILDING |
| AREA IS 61,250 AND THE PROPOSED TOTAL AREA IS 74.967. |
| TOTAL AREA PER FLOOR SHOULD BE NOTED ON THE PLAN, AND |
| THE TOTAL PROPOSED SHOULD NOT EXCEED THE TOTAL |
| PERMITTED.PLEASE CONTACT ME IF YOU NEED ASSISTANCE. |
| |
| 3.G0.0 CODE ANALYSIS, OCCUPANT LOAD SHOULD ROUND UP, |
| NOT ROUND DOWN, AS THERE CANNOT BE A FRACTION OF A |
| PERSON, AND OCCUPANT LOAD CANNOT BE LESS THAN FBC TABLE |
| 1004. |
| |
| 4.TOTAL SF AREA IS NOT CLEAR.THE CODE ANALYSIS, |
| 33545 SF PLUS 18400SF EQUALS 51945 SF, BUT THE TOTAL |
| (BUILDING AREA BREAKDOWN) IS 74,967.PLEASE CLARIFY |
| DISCREPANCY IN BUILDING AREA. |
| |
| 5. FBC1016.3(2), DEAD END CORRIDOR IS NOT TO EXCEED 50 |
| FEET, THE CORRIDOR BETWEEN ROOMS 109 AND 113 IS SHOWN |
| AS 65 FEET. |
| |
| 6. IT APPEARS THAT NEIL EDWIN DIXON IS SUCCESSOR |
| ARCHITECT TO GERALD TODD PERRODIN.PLEASE PROVIDE A |
| LETTER WHICH STATES THAT THE PROCEDURES OUTLINED IN |
| FAC61-18.002 HAVE BEEN FOLLOWED. |
| |
| 7. THE ORIGINAL PLAN DECLARED THE BREAK ROOM AREA AS |
| BUSINESS.REVISED A2.0B SHOWS SEVERAL ASSEMBLY AREAS, |
| BUT ASSEMBLY OCCUPANCY IS NOT ADDRESSED IN THE CODE |
| ANALYSIS.PLEASE REVISE EITHER A2.0B OR G0.0. |
| |
| 8.THE RETAIL PARTS AREA IS SHOWN AS RETAIL, DO YOU |
| MEAN MERCANTILE?CODE ANALYSIS ON G0.0 REFERS TO B AND |
| S1 OCCUPANCY ONLY.SEE FBC302 AND CLARIFY OCCUPANCY |
| CLASSIFICATION. |
| |
| 9. THE TRANSMITTAL LETTER STATES THAT 300 SF WAS ADDED. |
| PLEASE REVISE THE SITE PLAN A1.0 TO REFLECT THIS |
| CHANGE, FBC*106.PLEASE PROVIDE MORE INFORMATION; THE |
| TOTAL PROPOSED AREA IS STILL SHOWN AS 74, 967, BUT THE |
| CODE ANALYSIS SHOWS AN ADDITION 300 SF. |
| |
| 10. A2.2B NOTE AT K19 STATES THAT ACCESSIBLE PARKING |
| REVISIONS ARE SHOWN ON THE CIVIL DRAWINGS.PLEASE |
| INCORPORATE THESE CHANGES INTO THIS PLAN OR PROVIDE A |
| PERMIT NUMBER.I WAS UNABLE TO LOCATE THIS CHANGE. |
| |
| 11. A7.1, THE ELEVATIONS (DETAILS 1, 2, 3, ETC.) SHOW |
| CABINET DOORS; NOT CONSISTENT WITH DETAIL 13. |
| COMPLIANCE WITH FBC11-4.24 IS NOT CLEAR. |
| |
| 12. THE STRUCTURAL CALCS ARE TO INCLUDE A TITLE BLOCK |
| ON THE SIGNED AND SEALED SHEET, FAC61G15-23.002. |
| |
| 13.IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY, |
| 561-233-5025 DUE TO THE ADDITIONAL 300 SF BUSINESS |
| AREA. |
| |