2008-08-15 10:49:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PLEASE NOTE THAT, IN THE LAST REVISION, ONLY
 CHANGES CLOUDED WERE REVIEWED.SOME OF REVISION 15
 WERE INCLUDED IN REVISION 14 BUT NOT CLOUDED. THEREFORE
 SOME OF THE CHANGES WHICH WERE INADVERTENTLY PASSED
 UNDER REVISION 14 WERE NEVER REVIEWED AND MAY HAVE
 COMMENTS IN THIS REVIEW.
  
 PLEASE HAVE THE DESIGNER REVIEW THE PLANS AND CONFIRM
 THAT ALL CHANGES (FROM THE ISSUED PERMIT SET) ARE
 CLOUDED.
  
 2.PLEASE CLARIFY ALLOWABLE BUILDING AREA AND
 PROPOSED; SHEET G0.0 STATES THAT ALLOWABLE BUILDING
 AREA IS 61,250 AND THE PROPOSED TOTAL AREA IS 74.967.
 TOTAL AREA PER FLOOR SHOULD BE NOTED ON THE PLAN, AND
 THE TOTAL PROPOSED SHOULD NOT EXCEED THE TOTAL
 PERMITTED.PLEASE CONTACT ME IF YOU NEED ASSISTANCE.
  
 3.G0.0 CODE ANALYSIS, OCCUPANT LOAD SHOULD ROUND UP,
 NOT ROUND DOWN, AS THERE CANNOT BE A FRACTION OF A
 PERSON, AND OCCUPANT LOAD CANNOT BE LESS THAN FBC TABLE
 1004.
  
 4.TOTAL SF AREA IS NOT CLEAR.THE CODE ANALYSIS,
 33545 SF PLUS 18400SF EQUALS 51945 SF, BUT THE TOTAL
 (BUILDING AREA BREAKDOWN) IS 74,967.PLEASE CLARIFY
 DISCREPANCY IN BUILDING AREA.
  
 5. FBC1016.3(2), DEAD END CORRIDOR IS NOT TO EXCEED 50
 FEET, THE CORRIDOR BETWEEN ROOMS 109 AND 113 IS SHOWN
 AS 65 FEET.
  
 6. IT APPEARS THAT NEIL EDWIN DIXON IS SUCCESSOR
 ARCHITECT TO GERALD TODD PERRODIN.PLEASE PROVIDE A
 LETTER WHICH STATES THAT THE PROCEDURES OUTLINED IN
 FAC61-18.002 HAVE BEEN FOLLOWED.
  
 7. THE ORIGINAL PLAN DECLARED THE BREAK ROOM AREA AS
 BUSINESS.REVISED A2.0B SHOWS SEVERAL ASSEMBLY AREAS,
 BUT ASSEMBLY OCCUPANCY IS NOT ADDRESSED IN THE CODE
 ANALYSIS.PLEASE REVISE EITHER A2.0B OR G0.0.
  
 8.THE RETAIL PARTS AREA IS SHOWN AS RETAIL, DO YOU
 MEAN MERCANTILE?CODE ANALYSIS ON G0.0 REFERS TO B AND
 S1 OCCUPANCY ONLY.SEE FBC302 AND CLARIFY OCCUPANCY
 CLASSIFICATION.
  
 9. THE TRANSMITTAL LETTER STATES THAT 300 SF WAS ADDED.
 PLEASE REVISE THE SITE PLAN A1.0 TO REFLECT THIS
 CHANGE, FBC*106.PLEASE PROVIDE MORE INFORMATION; THE
 TOTAL PROPOSED AREA IS STILL SHOWN AS 74, 967, BUT THE
 CODE ANALYSIS SHOWS AN ADDITION 300 SF.
  
 10. A2.2B NOTE AT K19 STATES THAT ACCESSIBLE PARKING
 REVISIONS ARE SHOWN ON THE CIVIL DRAWINGS.PLEASE
 INCORPORATE THESE CHANGES INTO THIS PLAN OR PROVIDE A
 PERMIT NUMBER.I WAS UNABLE TO LOCATE THIS CHANGE.
  
 11. A7.1, THE ELEVATIONS (DETAILS 1, 2, 3, ETC.) SHOW
 CABINET DOORS; NOT CONSISTENT WITH DETAIL 13.
 COMPLIANCE WITH FBC11-4.24 IS NOT CLEAR.
  
 12. THE STRUCTURAL CALCS ARE TO INCLUDE A TITLE BLOCK
 ON THE SIGNED AND SEALED SHEET, FAC61G15-23.002.
  
 13.IMPACT FEES MAY BE DUE TO PALM BEACH COUNTY,
 561-233-5025 DUE TO THE ADDITIONAL 300 SF BUSINESS
 AREA.
  