Date |
Text |
2006-03-04 00:00:00 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| FBC-2004 BUILDING |
| FBC-2004 CHAPTER 11 |
| |
| 1. SHT A2.4B INDICATE VERTICAL |
| CONTRIBUTION TO EXISTING ROOF BY |
| EXTENDING PARAPET ABOVE EXISTING. |
| (ADJACENT TO ROOF AREA "A"). SHOW ADDED |
| SQUARE FOOTAGE. - ALSO INDICATE THE |
| METHOD OF SECONDARY ROOF DRAINAGE FOR |
| THE EXISTING ROOF BETWEEN COL. LINES F |
| THRU L, AND 3 THRU 9 WHERE NEW ROOF IS |
| LOCATED. SECTION 1107. |
| 2. SHT A2.4B MORE INFORMATION IS |
| REQUIRED ON THE ROOF DRAINS. IS THE |
| UPPER ROOF DRAINING DOWN TO THE LOWER |
| ROOF AREAS "I" & "H", OR ARE THOSE |
| OVERFLOW SCUPPERS NEAR COL LINES "Q-15", |
| "M-15", & "I-15"? PLEASE CLARIFY. |
| SECTION 106.1.1. |
| 3. SHT A2.4B ROOF AREAS F, E, C, B, & A. |
| STATE "SCUPPERS PER FIG. 1617.3" THAT IS |
| IN THE HIGH VELOCITY HURRICANE ZONE AND |
| IS APPROVED IN DADE/BROWARD COUNTYS |
| ONLY. SCUPPERS SHALL BE SIZED BY |
| SECTIONS 1101.7, 1107.3 AND TABLE |
| 1106.7. THE SIZING OF THE SCUPPERS CAN |
| NOT BE DETERMINED WITH OUT REFERENCE TO |
| THE DEFLECTION OF THE ROOF. PLEASE |
| INDICATE THIS IN YOUR SIZING |
| CALCULATIONS FOR THE SCUPPERS ON THE |
| PLANS. |
| 4. SHT A7.2 PLUMBING FIXTURES SCHEDULE |
| AND RESTROOM ACCESSORIES SCHEDULE ITEM |
| NUMBERS ARE NOT INDICATED ON ANY DETAIL. |
| PLEASE CLARIFY. SECTION 106.1.1. |
| 5. ACCESSIBLE LAVS: INDICATE COMPLIANCE |
| WITH 11-4.19.4 EXPOSED PIPES AND |
| SURFACES. |
| 6. SUBMIT A DETAIL FOR THE ACCESSIBLE |
| SHOWER SHOWING: |
| GRAB BARS PER FIGURE 37. 11-4.21.4 |
| SHOWER UNIT PER FIGURE 37. 11-4.21.6 |
| CURBS PER SECTION 11-4.21.7 |
| 7. SHT A7.0 GENERAL MANAGERS RESTROOM |
| SHALL BE ADAPTABLE AND AS SUCH IT MUST |
| SHOW A 5' TURNING AREA, BACKING FOR THE |
| GRAB BARS AT THE WATER CLOSET & SHOWER, |
| AS WELL AS A DETAIL FOR THE SHOWER |
| SHOWING THE LOCATION OF THE CONTROLS AND |
| INDICATE NO CURB ON THE SHOWER. SHOW THE |
| OPENING DIMENSIONS FOR THE WATER CLOSET |
| BETWEEN THE SHOWER AND THE VANITY FOR |
| THE LAV. |
| 8. BREAK ROOM SINK SHALL COMPLY WITH |
| 11-4.24 AND ALL SUBSECTIONS. SUBMIT A |
| DETAIL SHOWING COMPLIANCE WITH: |
| A. 11-4.24.2 HEIGHT |
| B. 11-4.24.3 KNEE CLEARANCE |
| C. 11-4.24.4 SINK DEPTH |
| D. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD |
| APPROACH, EXTENDING A MAXIMUM OF 19" |
| UNDERNEATH THE SINK REQUIRED). |
| E. 11-4.24.6 EXPOSED PIPES AND SURFACES |
| F. 11-4.24.7 FAUCETS |
| 9. SHT P0.1 PLUMBING NOTES: #1 |
| REFERENCES FBC-2001. ADOPTED CODE IS |
| FBC-2004. PLEASE CHANGE REFERENCE AND |
| DESIGN PER 2004 CODE. |
| 10. SHT P0.1 WATER HEATER DETAIL. |
| THERMAL EXPANSION CONTROL IS REQUIRED |
| PER SECTION 607.3.2. INDICATE METHOD. |
| 11. SHT P2.1.2 STORM OVERFLOW DRAIN LINE |
| WITH 10,900SF SHALL BE MINIMUM 10" PER |
| TABLE 106.3. PLEASE INDICATE ALL PIPE |
| SIZES AND SQUARE FOOTAGE AS IT |
| ACCUMULATES IN THE SYSTEM. |
| 12. SHT P2.1.2 NOTE "COMPRESSED AIR |
| DROPS BY OTHERS". SEPARATE PLANS AND |
| PERMIT REQUIRED FOR COMPRESSED AIR |
| SYSTEM. INDICATE MATERIAL TYPE FOR |
| COMPRESSED AIR ON PLANS. (SPECIALTY |
| DRAWINGS NOT SUBMITTED). |
| 13. SHT P2.2.2 LOWER ROOF (SHOWN AS 80SF |
| ON ARCHITECTURAL SHEETS) STORM DRAINAGE |
| PIPING IS NOT SHOWN. PLEASE SUBMIT STORM |
| PIPING FOR ROOF. PLEASE SUBMIT STORM |
| ISOMETRIC RISER DIAGRAMS FOR ALL |
| SECTIONS OF THE STORM SYSTEM SHOWING ALL |
| PIPE SIZES, CLEANOUTS, AND SQUARE |
| FOOTAGE AS IT ACCUMULATES IN THE SYSTEM |
| INCLUDING OVERFLOW SYSTEMS. SECTION |
| 106.3.5.1.3. |
| 14. SHT P5.1 DOMESTIC WATER RISER |
| DIAGRAM. WATER HAMMER ARRESTORS SHALL BE |
| LOCATED NEAR THE FIXTURE IN AN |
| "EFFECTIVE RANGE" NOT IN THE CEILING AS |
| SHOWN. PDI-WH 201 AND MANUF. INSTALL. |
| INSTRUCTIONS. (SEE PLUMBING NOTE #13 SHT |
| P0.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |