Plan Review Notes
Plan Review Notes For Permit 05111207
Permit Number 05111207
Review Stop M
Sequence Number 1
Notes
Date Text
2006-02-03 00:00:00DENIED:2004 FLORIDA BUILDING CODE
  
 1.PLAN SHEET M2.1.2, 16 X 14 RETURN
 AIR DUCT INTO LOCKER ROOM #145
 PENETRATES RATED RATED WALL BETWEEN THE
 LOCKER ROOM & SERVICE CENTER, NO FIRE
 DAMPER IS INDICATED.PLEASE CLARIFY.
  
 2.EQUIPMENT SCHEDULE INDICATES RTU 14
 & 15 (SERVICE GARAGE).THE EQUIPMENT
 SCHEDULE INDICATES A TOTAL OF OUTSIDE
 AIR 1040 CFM.PER 2004 FMC 404.2
 MINIMUM VENTILATION SHALL BE .05 CFM PER
 SQAURE FOOT & THE SYSTEM SHALL BE
 CAPABLE OF PRODUCING A VENTILATION RATE
 OF 1.5 CFM PER SQUARE FOOT.
  
 3.PLAN SHEET M2.2.2, PLEASE CLARIFY
 THE 'VEHICLE EXTRACTION SYSTEM FAN BY
 OTHERS'.WILL THIS HOOK-UP TO THE
 INDIVIDUAL MUFFLER EXHAUST?
  
 4.PLAN SHEET M8.1 SEQUENCE OF
 OPERATION ITEM 4 INDICATES THE GARAGE
 DOORS WILL BE NORMALLY CLOSED.IS THIS
 CORRECT?
  
 5.RTU-14 & RTU-15 WILL BE
 RECIRCULATING AIR FROM THE SERVICE AREA.
 PLEASE SHOW COMPLIANCE WITH 2004 FBC
 406.6.
  
 6.PLEASE CLARIFY IF THE ALARMS FOR THE
 CO & FV SENSORS ARE TIED TO THE FIRE
 ALARM.
  
 7.PLEASE PROVIDE SUBMITTAL FOR THE
 FLAMMABLE VAPOR SENSOR & THE CARBON
 MONOXIDE SENSOR.PLEASE NOTE, TESTING
 OF SENSORS REQUIRED FOR FINAL
 INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.
  
  
  
  