2006-02-03 00:00:00 | DENIED:2004 FLORIDA BUILDING CODE |
| |
| 1.PLAN SHEET M2.1.2, 16 X 14 RETURN |
| AIR DUCT INTO LOCKER ROOM #145 |
| PENETRATES RATED RATED WALL BETWEEN THE |
| LOCKER ROOM & SERVICE CENTER, NO FIRE |
| DAMPER IS INDICATED.PLEASE CLARIFY. |
| |
| 2.EQUIPMENT SCHEDULE INDICATES RTU 14 |
| & 15 (SERVICE GARAGE).THE EQUIPMENT |
| SCHEDULE INDICATES A TOTAL OF OUTSIDE |
| AIR 1040 CFM.PER 2004 FMC 404.2 |
| MINIMUM VENTILATION SHALL BE .05 CFM PER |
| SQAURE FOOT & THE SYSTEM SHALL BE |
| CAPABLE OF PRODUCING A VENTILATION RATE |
| OF 1.5 CFM PER SQUARE FOOT. |
| |
| 3.PLAN SHEET M2.2.2, PLEASE CLARIFY |
| THE 'VEHICLE EXTRACTION SYSTEM FAN BY |
| OTHERS'.WILL THIS HOOK-UP TO THE |
| INDIVIDUAL MUFFLER EXHAUST? |
| |
| 4.PLAN SHEET M8.1 SEQUENCE OF |
| OPERATION ITEM 4 INDICATES THE GARAGE |
| DOORS WILL BE NORMALLY CLOSED.IS THIS |
| CORRECT? |
| |
| 5.RTU-14 & RTU-15 WILL BE |
| RECIRCULATING AIR FROM THE SERVICE AREA. |
| PLEASE SHOW COMPLIANCE WITH 2004 FBC |
| 406.6. |
| |
| 6.PLEASE CLARIFY IF THE ALARMS FOR THE |
| CO & FV SENSORS ARE TIED TO THE FIRE |
| ALARM. |
| |
| 7.PLEASE PROVIDE SUBMITTAL FOR THE |
| FLAMMABLE VAPOR SENSOR & THE CARBON |
| MONOXIDE SENSOR.PLEASE NOTE, TESTING |
| OF SENSORS REQUIRED FOR FINAL |
| INSPECTION. |
| |