2005-12-31 00:00:00 | IN ELEC FOR REVIEW |
| ********* UNSAT ********** |
| |
| 1)NOTE: PLANS SHOULD INCLUDE CURRENT |
| CODES RELEVANT TO PLANS/DESIGN AND SCOPE |
| OF WORK. |
| PLEASE KNOW, AS OF OCT 1ST, 2005 THE FBC |
| HAS CHANGED TO THE 2004 FBC WITH OTHER |
| ADOPTED CODES. |
| PLEASE HAVE PLANS REFLECT THE 2002 |
| NFPA-70(NEC). |
| 2003 NFPA-101 , 2002 NFPA-72. |
| PLEASE SEE OTHER REVIEWER(S) NOTES. |
| |
| 2)NOTE: PLEASE PROVIDE INFORMATION FOR |
| OPERATION OF NEW GATES IN THE EVENT OF |
| POWER FAILURE. PLEASE ALSO SEE POSSIBLE |
| FIRE DEPT NOTES PERAINING TO MIN WIDTHS |
| REQUIRED . |
| |
| 3)NOTE: PLEASE SEE 230.2(C) FOR OTHER |
| SERVICES PERMITTED. PLEASE PROVIDE |
| INFORMATION FOR EXISTING SERVICE SIZE, |
| AS THE SAME VOLTAGES APPEAR TO BE |
| PRESENT. PLEASESECOND SERVICE NEEDS TO |
| BE VERIFIED FOR GRANTING ANY SPECIAL |
| PERMISSION FOR ADDING SERVICE. IT IS |
| NOTED THAT THE EXISITNG MAIN AND NEW |
| MAIN WILL BE GROUPED IN THE SAME |
| LOCATION. |
| |
| 4)NOTE: PLEASE SEE LS 101 7.8,700.6 , |
| 90.4 AN EMERGENCY BATTERY BACK UP |
| FIXTURE OF SOME TYOE IS BEING REQUESTED |
| TO BE ADDED TO MAIN ELECTRICAL ROOM |
| UNLESS ONE IS ALREADY PRESENT. |
| |
| 5)NOTE: PLEASE SEE MIN FEEDER SIZES FOR |
| PANELS SRA, SRB AND GA SHALL BE SIZED |
| PER 310.16. 3/0'S RATED AT 200A'S (75 |
| DEGREE COL) AND OCP IN NEW DPA IS SHOWN |
| AT 225A'S. 4/0'S MIN. |
| 240.4,310.16,110.14 |
| |
| 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| AND LARGEST MOTOR LOADS AT 125%. |
| PLEASE SHOW ON EACH PANEL AND ON MAIN |
| SERVICE CALCS. |
| 215.3,230.42 ETC. |
| |
| 7)NOTE: PLEASE SPECIFY ALL AREAS IN |
| SERVICE BAYS PER NEC 511, 511.7 A,B ETC. |
| PLEASE PROVIDE A LAYOUT AND SPECS FOR |
| ALL ELECTRICAL DEVICES, LIGHTING ETC. |
| ** PLEASE SEE NOTES PERTAINING TO MIN |
| AIR CHANGES PER OTHER REVIEWERS. |
| PLEASE SEE NEW ELECTRICAL PANELS SHOWN |
| IN THESE AREAS ALSO, MIN HEIGHTS ETC, |
| |
| ** PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| OTHER REIVEWERS WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |