Plan Review Notes
Plan Review Notes For Permit 05111207
Permit Number 05111207
Review Stop E
Sequence Number 1
Notes
Date Text
2005-12-31 00:00:00IN ELEC FOR REVIEW
 ********* UNSAT **********
  
 1)NOTE: PLANS SHOULD INCLUDE CURRENT
 CODES RELEVANT TO PLANS/DESIGN AND SCOPE
 OF WORK.
 PLEASE KNOW, AS OF OCT 1ST, 2005 THE FBC
 HAS CHANGED TO THE 2004 FBC WITH OTHER
 ADOPTED CODES.
 PLEASE HAVE PLANS REFLECT THE 2002
 NFPA-70(NEC).
 2003 NFPA-101 , 2002 NFPA-72.
 PLEASE SEE OTHER REVIEWER(S) NOTES.
  
 2)NOTE: PLEASE PROVIDE INFORMATION FOR
 OPERATION OF NEW GATES IN THE EVENT OF
 POWER FAILURE. PLEASE ALSO SEE POSSIBLE
 FIRE DEPT NOTES PERAINING TO MIN WIDTHS
 REQUIRED .
  
 3)NOTE: PLEASE SEE 230.2(C) FOR OTHER
 SERVICES PERMITTED. PLEASE PROVIDE
 INFORMATION FOR EXISTING SERVICE SIZE,
 AS THE SAME VOLTAGES APPEAR TO BE
 PRESENT. PLEASESECOND SERVICE NEEDS TO
 BE VERIFIED FOR GRANTING ANY SPECIAL
 PERMISSION FOR ADDING SERVICE. IT IS
 NOTED THAT THE EXISITNG MAIN AND NEW
 MAIN WILL BE GROUPED IN THE SAME
 LOCATION.
  
 4)NOTE: PLEASE SEE LS 101 7.8,700.6 ,
 90.4 AN EMERGENCY BATTERY BACK UP
 FIXTURE OF SOME TYOE IS BEING REQUESTED
 TO BE ADDED TO MAIN ELECTRICAL ROOM
 UNLESS ONE IS ALREADY PRESENT.
  
 5)NOTE: PLEASE SEE MIN FEEDER SIZES FOR
 PANELS SRA, SRB AND GA SHALL BE SIZED
 PER 310.16. 3/0'S RATED AT 200A'S (75
 DEGREE COL) AND OCP IN NEW DPA IS SHOWN
 AT 225A'S. 4/0'S MIN.
 240.4,310.16,110.14
  
 6)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AND LARGEST MOTOR LOADS AT 125%.
 PLEASE SHOW ON EACH PANEL AND ON MAIN
 SERVICE CALCS.
 215.3,230.42 ETC.
  
 7)NOTE: PLEASE SPECIFY ALL AREAS IN
 SERVICE BAYS PER NEC 511, 511.7 A,B ETC.
 PLEASE PROVIDE A LAYOUT AND SPECS FOR
 ALL ELECTRICAL DEVICES, LIGHTING ETC.
 ** PLEASE SEE NOTES PERTAINING TO MIN
 AIR CHANGES PER OTHER REVIEWERS.
 PLEASE SEE NEW ELECTRICAL PANELS SHOWN
 IN THESE AREAS ALSO, MIN HEIGHTS ETC,
  
 ** PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER REIVEWERS WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  