Plan Review Notes
Plan Review Notes For Permit 05111207
Permit Number 05111207
Review Stop B
Sequence Number 1
Notes
Date Text
2006-03-16 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 1.)A NOTICE OF COMMENCEMENT MUST BE
 FILED WITH THE CLERK OF COURTS BEFORE A
 PERMIT CAN BE ISSUED.THE NOC PROVIDED
 DOES NOT HAVE THE RECORDING STAMP
 SHOWING BOOK AND PAGE.
  
 2.)ENERGY CALCS ARE TO BE SIGNED AND
 SEALED, FBC13-103.1.1.1.
  
 3.)ENERGY CALCS TO BE SIGNED IN THE
 OWNER/AGENT LINE FBC13-103.1.
  
 4.)THE ENGINEERING CALCULATIONS
 PREPARED BY TLC ARE TO INCLUDE THE CA
 NUMBER, FAC61G15-23.002.
  
 5.)ENGINEERING CALCULATIONS ARE TO BE
 SIGNED AND SEALED ON EACH SHEET OR TO
 HAVE AN INDEX SHEET, FAC61G15-23-002.
 THIS HAS BEEN DISCUSSED WITH FBPE;
 PLEASE CONTACT THEM IF YOU NEED
 CLARIFICATION.
  
 6.)THE STRESS INCREASE SHOWN ON SHEET
 11 OF 49 IN THE STRUCTURAL CALCS IS NOT
 PERMITTED, FBC1605.3.1.1(2).
  
 7.)SHEET 32 OF 49 OF THE STRUCTURAL
 CALCS REFER TO ASCE7 98, SHOULD BE ASCE7
 02, FBC35.
  
 8.)SHEET G0.0 DECLARES THE STORAGE AND
 AUTO REPAIR AREA AS S1 NON SEPARATED
 USES.SEE FBC302.1.1, INCIDENTAL USES
 SHALL BE CLASSIFIED IN ACCORDANCE WITH
 THE MAIN OCCUPANCY OR SEPARATED FBC
 TABLE 302.1.1, OR MIXED OCCUPANCY FBC
 TABLE 302.3.2.
  
 9.)PLANS SHOW A 2 HOUR SEPARATION
 BETWEEN THE S1 AND B AREAS, FBC TABLE
 302.3.2 REQUIRES 3 HOUR.
  
 10.)PROVIDE AREA CALCULATIONS ON SHEET
 G0.00; EXISTING SF, DEMO SF, ADDITION,
 NEW TOTAL.THIS SHOULD BE DONE PRIOR TO
 IMPACT FEE ASSESSMENT.
  
 11.)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY.THE PLANS MUST BE STAMPED
 AND THE RECEIPT ATTACHED TO THE
 APPLICATION.233-5025 FOR MORE
 INFORMATION.
  
 12.)SHEET A2.0B, NO EXIT LIGHT SHOWN
 AT EXIT 5.
  
 13.)ACCESSIBLE PARKING IS TO COMPLY
 WITH CITY OF WEST PALM BEACH STANDARD,
 SEE ATTACHED.
  
 14.)FIRST FLOOR LIFE SAFETY PLAN SHOWS
 THE PATH OF TRAVEL FROM PARTS INVENTORY
 LEADING TO EXIT 9.THIS SHOULD BE
 MEASURED TO AN ACCESSIBLE EXIT (EXIT 9
 SHOWS A STEP), FBC11-4.13(9).WHEN
 MEASURED FROM FARTHER AWAY FROM THE
 POINT SHOWN ON THE PLAN TO EXIT 7, THE
 DISTANCE APPEARS GREATER THAN THE 200FT
 ALLOWED.
  
 15.)THE SECOND FLOOR IS REFERRED TO AS
 BOTH A SECOND FLOOR AND A MEZZANINE.
 FBC505, IS THIS A MEZZANINE OR A SECOND
 FLOOR?
  
 16.)IS THE COVERED OPEN AREA BETWEEN
 THE TWO EXISTING BUILDINGS INCLUDED IN
 THE BUILDING AREA?SEE FBC CHAPTER 2,
 DEFINITION OF BUILDING AREA.
  
 17.)DECLARE AN OCCUPANCY FOR THE OPEN
 AREA, FBC406.SHOW REQUIRED OCCUPANCY
 SEPARATION.
  
 18.)PROVIDE A SOILS INVESTIGATION
 REPORT, FBC1802.2.1.
  
 19.)PRODUCT APPROVALS REQUIRED FOR ALL
 COMPONENTS AND CLADDING, INCLUDING THE
 EIFS SYSTEM, FAC9B72.FLORIDA STATE OR
 LOCAL PRODUCT APPROVALS REQUIRED,
 FAC9B72.WWW.FLORIDABUILDING.ORG
 PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD, FBC*106.3.3.
  
 20.)FA6.0 REFERS TO A CODE FROM
 FBC2001, REGARDING SIGNAGE.PLEASE
 REVISE.
  
 21.)CA6.0 DOES NOT SPECIFY THE 2 HOUR
 UL LISTED BLOCK REQUIRED IN THE
 ASSEMBLY.CHECK ALL UL DETAILS.
 FAILURE TO DO SO WILL RESULT IN THE
 PLANS BEING FAILED IF THEY ARE SUBMITTED
 WITH INCORRECT INFORMATION ON OTHER
 ASSEMBLIES.
  
 22.)ID11.9, THE BREAK ROOM SINK IS TO
 BE ACCESSIBLE, FBC11-4.24.
  
 23.)PROVIDE DESIGN CRITERIA FOR
 INTERIOR FINISHES, FBC TABLE 803.5.
  
 24.)S1.1 REFERS TO ASCE7-98, SHOULD BE
 ASCE7-02, FBC35.
  
 25.)M01 REFERS TO FBC2001, SPECIAL
 NOTES.
  
 26.)M7.1 REFERS TO FBC2001.CLEARANCE
 FOR MECHANICAL EQUIPMENT IS TO COMPLY
 WITH FBC1509.7.
  
 27.) M7.1 DETAIL 6 SHOWS WOOD BLOCKING.
 NONCOMBUSTIBLE ONLY ALLOWED, FBC CHAPTER
 6.
  
  