2006-03-16 00:00:00 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 |
| EXISTING BUILDING CODE |
| FBC*CITY OF WEST PALM BEACH |
| AMENDMENTS TO THE FBC2004 |
| |
| 1.)A NOTICE OF COMMENCEMENT MUST BE |
| FILED WITH THE CLERK OF COURTS BEFORE A |
| PERMIT CAN BE ISSUED.THE NOC PROVIDED |
| DOES NOT HAVE THE RECORDING STAMP |
| SHOWING BOOK AND PAGE. |
| |
| 2.)ENERGY CALCS ARE TO BE SIGNED AND |
| SEALED, FBC13-103.1.1.1. |
| |
| 3.)ENERGY CALCS TO BE SIGNED IN THE |
| OWNER/AGENT LINE FBC13-103.1. |
| |
| 4.)THE ENGINEERING CALCULATIONS |
| PREPARED BY TLC ARE TO INCLUDE THE CA |
| NUMBER, FAC61G15-23.002. |
| |
| 5.)ENGINEERING CALCULATIONS ARE TO BE |
| SIGNED AND SEALED ON EACH SHEET OR TO |
| HAVE AN INDEX SHEET, FAC61G15-23-002. |
| THIS HAS BEEN DISCUSSED WITH FBPE; |
| PLEASE CONTACT THEM IF YOU NEED |
| CLARIFICATION. |
| |
| 6.)THE STRESS INCREASE SHOWN ON SHEET |
| 11 OF 49 IN THE STRUCTURAL CALCS IS NOT |
| PERMITTED, FBC1605.3.1.1(2). |
| |
| 7.)SHEET 32 OF 49 OF THE STRUCTURAL |
| CALCS REFER TO ASCE7 98, SHOULD BE ASCE7 |
| 02, FBC35. |
| |
| 8.)SHEET G0.0 DECLARES THE STORAGE AND |
| AUTO REPAIR AREA AS S1 NON SEPARATED |
| USES.SEE FBC302.1.1, INCIDENTAL USES |
| SHALL BE CLASSIFIED IN ACCORDANCE WITH |
| THE MAIN OCCUPANCY OR SEPARATED FBC |
| TABLE 302.1.1, OR MIXED OCCUPANCY FBC |
| TABLE 302.3.2. |
| |
| 9.)PLANS SHOW A 2 HOUR SEPARATION |
| BETWEEN THE S1 AND B AREAS, FBC TABLE |
| 302.3.2 REQUIRES 3 HOUR. |
| |
| 10.)PROVIDE AREA CALCULATIONS ON SHEET |
| G0.00; EXISTING SF, DEMO SF, ADDITION, |
| NEW TOTAL.THIS SHOULD BE DONE PRIOR TO |
| IMPACT FEE ASSESSMENT. |
| |
| 11.)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY.THE PLANS MUST BE STAMPED |
| AND THE RECEIPT ATTACHED TO THE |
| APPLICATION.233-5025 FOR MORE |
| INFORMATION. |
| |
| 12.)SHEET A2.0B, NO EXIT LIGHT SHOWN |
| AT EXIT 5. |
| |
| 13.)ACCESSIBLE PARKING IS TO COMPLY |
| WITH CITY OF WEST PALM BEACH STANDARD, |
| SEE ATTACHED. |
| |
| 14.)FIRST FLOOR LIFE SAFETY PLAN SHOWS |
| THE PATH OF TRAVEL FROM PARTS INVENTORY |
| LEADING TO EXIT 9.THIS SHOULD BE |
| MEASURED TO AN ACCESSIBLE EXIT (EXIT 9 |
| SHOWS A STEP), FBC11-4.13(9).WHEN |
| MEASURED FROM FARTHER AWAY FROM THE |
| POINT SHOWN ON THE PLAN TO EXIT 7, THE |
| DISTANCE APPEARS GREATER THAN THE 200FT |
| ALLOWED. |
| |
| 15.)THE SECOND FLOOR IS REFERRED TO AS |
| BOTH A SECOND FLOOR AND A MEZZANINE. |
| FBC505, IS THIS A MEZZANINE OR A SECOND |
| FLOOR? |
| |
| 16.)IS THE COVERED OPEN AREA BETWEEN |
| THE TWO EXISTING BUILDINGS INCLUDED IN |
| THE BUILDING AREA?SEE FBC CHAPTER 2, |
| DEFINITION OF BUILDING AREA. |
| |
| 17.)DECLARE AN OCCUPANCY FOR THE OPEN |
| AREA, FBC406.SHOW REQUIRED OCCUPANCY |
| SEPARATION. |
| |
| 18.)PROVIDE A SOILS INVESTIGATION |
| REPORT, FBC1802.2.1. |
| |
| 19.)PRODUCT APPROVALS REQUIRED FOR ALL |
| COMPONENTS AND CLADDING, INCLUDING THE |
| EIFS SYSTEM, FAC9B72.FLORIDA STATE OR |
| LOCAL PRODUCT APPROVALS REQUIRED, |
| FAC9B72.WWW.FLORIDABUILDING.ORG |
| PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| DESIGNER OF RECORD, FBC*106.3.3. |
| |
| 20.)FA6.0 REFERS TO A CODE FROM |
| FBC2001, REGARDING SIGNAGE.PLEASE |
| REVISE. |
| |
| 21.)CA6.0 DOES NOT SPECIFY THE 2 HOUR |
| UL LISTED BLOCK REQUIRED IN THE |
| ASSEMBLY.CHECK ALL UL DETAILS. |
| FAILURE TO DO SO WILL RESULT IN THE |
| PLANS BEING FAILED IF THEY ARE SUBMITTED |
| WITH INCORRECT INFORMATION ON OTHER |
| ASSEMBLIES. |
| |
| 22.)ID11.9, THE BREAK ROOM SINK IS TO |
| BE ACCESSIBLE, FBC11-4.24. |
| |
| 23.)PROVIDE DESIGN CRITERIA FOR |
| INTERIOR FINISHES, FBC TABLE 803.5. |
| |
| 24.)S1.1 REFERS TO ASCE7-98, SHOULD BE |
| ASCE7-02, FBC35. |
| |
| 25.)M01 REFERS TO FBC2001, SPECIAL |
| NOTES. |
| |
| 26.)M7.1 REFERS TO FBC2001.CLEARANCE |
| FOR MECHANICAL EQUIPMENT IS TO COMPLY |
| WITH FBC1509.7. |
| |
| 27.) M7.1 DETAIL 6 SHOWS WOOD BLOCKING. |
| NONCOMBUSTIBLE ONLY ALLOWED, FBC CHAPTER |
| 6. |
| |
| |