Date |
Text |
2005-12-22 00:00:00 | 1) (2004 FBC) 106.1.1 INFORMATION ON |
| CONSTRUCTION DOCUMENTS. CONSTRUCTION |
| DOCUMENTS SHALL BE OF SUFFICIENT CLARITY |
| TO INDICATE THE LOCATION, NATURE & |
| EXTENT OF THE WORK PROPOSED & SHOW IN |
| DETAIL THAT IT WILL CONFORM TO THE |
| PROVISIONS OF THIS CODE AND REVELENT |
| LAWS, ORDINANCES, AND RULES AND |
| REGULATIONS AS DETERMINED BY THE |
| BUILDING OFFICIAL. |
| |
| 2) 1609.1.4 IN WIND BORNE DEBRIS |
| REGIONS, EXTERIOR GLAZING THAT RECEIVES |
| POSITIVE PRESSURE IN BUILDINGS SHALL BE |
| ASSUMED TO BE OPENINGS UNLESS SUCH |
| GLAZING IS IMPACT RESISTANT OR PROTECTED |
| WITH AN IMPACT RESISTANT COVERING MEET- |
| ING THE REQUIREMENTS OF SSTD 12, ASTM |
| E 1886 AND ASTM E 1996 OR MIAMI-DADE. |
| ALSO SEE FLORIDA EXISTING BUILDING CODE |
| BOOK SEC.507.3 |
| |
| 1) GLAZED OPENINGS LOCATED WITHIN 30FT |
| OF GRADE SHALL MEET THE REQUIREMENTS OF |
| LARGE MISSLE TEST. |
| 2) GLAZED OPENINGS LOCATED MORE THAN |
| 30FEET ABOVE GRADE SHALL MEET THE |
| PROVISIONS OF THE SMALL MISSILE TEST. |
| |
| 3) PROVIDE STORM PANEL INFORMATION WITH |
| INSTALLATION SCHEDULE AND KEY PLAN WITH |
| SPECIFIC ANCHORS AND MOUNTING TO BE USED |
| FOR ALL NON-IMPACT GLAZING. |
| FBC 2004 TABLE 1609.1.4 |
| |
| |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| TEL:(561) 805-6726 |
| |
| |