Plan Review Notes
Plan Review Notes For Permit 05111183
Permit Number 05111183
Review Stop B
Sequence Number 4
Notes
Date Text
2006-05-24 00:00:00BUILDING REVISION CHECKLIST:
 1- ITEM 3(B) OF PROVISO DATED 4-18-06
 REQUIRED ARCHITECT TO REVISE CONNECTOR
 HTS 20 FOR GIRDER TRUSS THAT RUNS FROM
 BREAKFAST AREA TO POWDER ROOM (SEE
 COMMENTS ON SHEET A-5.0). HTS 20 IS A
 WOOD TO WOOD CONNECTOR. NEED TO SPECIFY
 A WOOD TO MASONRY CONNECTOR. SEE SIMPSON
 CATALOGUE FOR PROPER MASONRY CONNECTORS
 AND REVISE AS REQUIRED.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.