Plan Review Notes For Permit 05111183 |
Permit Number |
05111183 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-04-19 00:00:00 | BUILDING REVIEW PROVISO: | | 1- PROVIDE COMPLETE INFORMATION FOR | | STORM SHUTTERS UNDER A SEPARATE PERMIT | | AS REQUESTED BY CONTRACTOR. | | 2- PROVIDE FLORIDA OR LOCAL PRODUCT | | APPROVAL UNDER A SEPARATE PERMIT FOR | | 6' X 8' OVERHEAD GARAGE DOOR THAT MEETS | | THE DESIGN PRESSURES CALCULATED BY THE | | ARCHITECT. SEE PLANS. | | 3- SHEET A-5.0: A) REVISE DETAILS 4 | | AND 5. SEE CATALOGUE TO MATCH PROPER | | CONNECTOR SIZE AND NUMBER OF NAILS. | | B) REVISE CONNECTORS SPECIFIED FOR BOTH | | ENDS OF GIRDER TRUSS THAT RUNS FROM | | BREAKFAST AREA TO POWDER ROOM. SPECIFY | | CONNECTORS THAT MEET THE CALCULATED | | UPLIFT LOADS AND MAKE SURE CONNECTORS | | ARE WOOD TO MASONRY INSTALLATION. HTS 20 | | IS NOT A WOOD TO MASONRY CONNECTOR. | | 4- SHEET D-1: A) REVISE WOOD FRAMING | | DETAIL TO MATCH, ROOF FRAMING PLAN AND | | DETAIL 4, 5 AND 7. | | B) DETAILS 4 AND 7: SPECIFY HOW MUCH | | EMBEDMENT IS REQ'D FOR 3/4" ANCHOR BOLTS |
|