2005-12-29 00:00:00 | BUILDING REVIEW CHECKLIST: |
| 1- ALL PLANS SUBMITTED AFTER OCTOBER 1ST |
| 2005 ARE REQUIRED TO COMPLY WITH FBC |
| 2004. REVISE ALL PLANS, GENERAL NOTES, |
| DESIGN PARAMETERS, CONSTRUCTION TYPE AND |
| ALL PERTINENT ITEMS SHOWN ON PLANS AS |
| REQUIRED TO COMPLY WITH FBC 2004. |
| |
| 2- TRUSS DESIGN DRAWINGS NEED TO BE |
| PROVIDED TO THE BUILDING OFFICIAL FOR |
| APPROVAL PRIOR TO INSTALLATION. SEC. |
| R802.10.1 RESIDENTIAL FBC 2004. |
| (REMAINDER: DESIGNER OF RECORD TO REVIEW |
| ALL TRUSSES PRIOR TO SUBMITTAL TO THIS |
| OFFICE). |
| |
| 3- DESIGNER OF RECORD TO REVIEW ALL |
| PRODUCT APPROVALS PRIOR TO SUBMITTAL TO |
| THIS OFFICE AS REQUIRED BY SEC. 106.3.3 |
| CITY AMENDMENTS TO FBC 2004. |
| |
| 4- PROVIDE ALL INFORMATION ON PLANS |
| REGARDING THE SEPARATION AND OPENING |
| PROTECTION AS REQUIRED BY SEC. R309 OF |
| RESIDENTIAL FBC 2004. |
| |
| 5- NEED RECORDED NOTICE OF COMMENCEMENT. |
| |
| 6- PROVIDE FLORIDA OR LOCAL PRODUCT |
| APPROVAL FOR: |
| A) TRUSS CONNECTORS SPECIFIED ON |
| PLANS. PROVIDE ONLY THE COVER PAGE AND |
| PAGES SHOWING THE SPECIFIC CONNECTOR |
| SPECIFIED ON PLANS. PLEASE DON'T SUBMIT |
| COMPLETE REPORT TO EXPEDITE REVIEW |
| PROCESS AND SAVE PAPER. |
| |
| B) GARAGE DOORS: FLORIDA NUMBER |
| SUBMITTED IS NOT LONGER LISTED. |
| |
| C) 2" WINDOW MULLION: NEED CURRENT |
| DADE COUNTY NOA THAT MATCHES ONE |
| SUBMITTED FOR FLORIDA APPROVAL. |
| |
| D) FIXED WINDOWS: MISSING FLORIDA |
| PRODUCT APPROVAL. |
| |
| E) ATRIUM DOOR: SEE PLANS FOR SIZE AND |
| DOOR SWING DIRECTION. |
| |
| 7- SOIL TEST REPORT WAS DONE BASED ON |
| FBC 2001. NEED CURRENT SOIL TEST REPORT |
| COMPLYING WITH FBC 2004. |
| |
| JULIO GOMEZ |
| BUILDING PLANS EXAMINER |