2006-03-04 00:00:00 | 1)CITY OF WPB AMENDMENTS.106.3.3 |
| PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL.THESE ITEMS |
| INCLUDE EXTERIOR DOORS, WINDOWS,ALL |
| ROOFING PRODUCTS,STRUCTURAL |
| COMPONENTS, ETC.TWO COPIES OF EACH IS |
| REQUIRED ALONG WITH THE STATE COVER |
| SHEET AND FL#. THE ONLY PRODUCT APPROVAL |
| SUBMITTED IS FOR THE EXTERIOR |
| DOOR. |
| |
| 2) INDICATE THE HIEGHT AND WIDTH |
| DIMENTIONS OF THE NEW PORCH. ALSO |
| INDICATE THE LOWEST HEADROOM OF THE |
| PORCH.SEE WPB AMENDMENTS 106.1.1 |
| |
| 3)MORE INFORMATION IS REQUIRED FOR THE |
| HURRICANE STRAPS. WHAT'S THE UP-LIFT |
| PRESSURES OF THESE STRAPS? THIS |
| INFORMATION IS REQUIRED ON THE DRAWINGS. |
| |
| 4) SHEET A2.1 REFERS TO CERTAIN |
| DETAILS,BUT THERE ARE NO REFERENCE |
| NUMBERS IN THE SYMBOL. |
| |
| 5) TRUSS DRAWINGS SHALL PE BROVIDED TO |
| THE BUILDING OFFICIAL AND APPROVED PRIOR |
| TO INSTALLATION. R802.10.1 |
| |
| 6) THE FINISH SCHEDULE ON SHEET A2.1 |
| INDICATES ALL CEILING HEIGHT AT 9'. HOW |
| WILL THIS BE ACCOMPLISH IF THE |
| DIMENTIONS ON SHEET A2.3 ARE USED. |
| INDICATE THE CORRECT FINISH CEILING |
| HEIGHT OF EACH ROON ON THE DRAWINGS. |
| SEE R305.1 FOR ADDITIONAL INFORMATION. |
| |
| 7) ON SHEET A2.3 DRAWING #2, THE 3/4" |
| SCALE DOES NOT REFLECT THE CORRECT |
| DIMENTIONS.CLARIFY. |
| |