Plan Review Notes
Plan Review Notes For Permit 05111165
Permit Number 05111165
Review Stop P
Sequence Number 1
Notes
Date Text
2005-12-20 00:00:00DENIED;
 1. PLEASE DELETE GAS RISER DIAGRAM OR
 COMPLY WITH THE FOLLOWING REQUIREMENTS;
 SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 TYPE OF GAS, (LP OR NATURAL)
 BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.5.2 AND TABLES 402(1) THRU
 402(34).
 INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
 2.SANITARY RISER DIAGRAM NOT TO CODE;
 FIRST FLOOR W/C NOT VENTED AS DRAWN.
 LAV. TO DISCHARGE SEPARATE FROM W/M. SEE
 ONE SET OF PLANS MARKED IN RED.
 3.IS WATER HEATER IN ROOM 108? PLEASE
 SHOW ON DRAWING. ALSO SHOW MAKEUP AIR
 FOR W/H PER. SEC. 304 FBC-2004 FUEL GAS.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695