2005-12-20 00:00:00 | DENIED; | | 1. PLEASE DELETE GAS RISER DIAGRAM OR | | COMPLY WITH THE FOLLOWING REQUIREMENTS; | | SUBMIT AN ISOMETRIC DRAWING THAT | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | AND CORRESPONDING LENGTHS PER FBC-2004 | | FUEL GAS CODE. | | TYPE OF GAS, (LP OR NATURAL) | | BTU LOAD OF EACH APPLIANCE AND THE | | TOTAL BTU LOAD ON THE SYSTEM. REFER TO | | THE FBC-2004 FUEL GAS CODE SECS. 401.8 | | THRU 402.5.2 AND TABLES 402(1) THRU | | 402(34). | | INDICATE THE DELIVERY PRESSURE (PSI) | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. | | 2.SANITARY RISER DIAGRAM NOT TO CODE; | | FIRST FLOOR W/C NOT VENTED AS DRAWN. | | LAV. TO DISCHARGE SEPARATE FROM W/M. SEE | | ONE SET OF PLANS MARKED IN RED. | | 3.IS WATER HEATER IN ROOM 108? PLEASE | | SHOW ON DRAWING. ALSO SHOW MAKEUP AIR | | FOR W/H PER. SEC. 304 FBC-2004 FUEL GAS. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|