Plan Review Notes
Plan Review Notes For Permit 05111146
Permit Number 05111146
Review Stop B
Sequence Number 3
Notes
Date Text
2006-08-05 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC* CITY OF WEST PALM BEACH AMENDMENTS
 TO THE FBC2004
  
 1.)THE NEW ANCHOR SCHEDULE SPECIFIES
 PRESSURES OF -57, 12" ANCHOR SPACING.
 YOU HAVE HIGHLIGHTED -60 ON PAGE 10 FOR
 DESIGN PRESSURE BUT ALSO HIGHLIGHTED 12"
 WHICH IS IN THE -40 COLUMN.-60
 REQUIRES 10" OR CLOSER ANCHOR SPACING,
 DEPENDING ON SHUTTER SPAN, NOT 12".