Plan Review Notes
Plan Review Notes For Permit 05111131
Permit Number 05111131
Review Stop P
Sequence Number 1
Notes
Date Text
2005-12-20 00:00:00DENIED
 REFERENCE: FBC-2004 424.2 SWIMMING POOLS
  
 1) FBC-2004 SEC 424.2.6.1 ENGINEERING
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-5. (ADD TO NOTES)
 2) FBC-2004 424.2.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (DETAIL)
 3) FBC-2004 SEC 424.2.9 WATER SUPPLY,
 LOCAL ORD.#2853-95, BACKFLOW REQUIRED ON
 WATER SERVICE. (ADD TO NOTES)
 4) FBC-2004 424.2.12.1 PRESSURE TESTS.
 PER MANUFACTURE RECOMMENDATIONS, NO AIR
 TEST SHALL BE APPROVED FOR PVC PIPE AND
 FITTINGS. (ADD TO NOTES)
 5) FBC-2004 SEC 424.2.13.2 JOINTS AND
 CONNECTIONS, FBC PLMG SEC 605.21 PURPLE
 PRIMER REQUIRED ON PVC PIPING. (ADD TO
 NOTES)
 6) FBC-2004 SEC 424.2.14.2 WATER
 RETENTION PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE CUT SHEETS
 SUBMITTAL)
 7) CITY OF WEST PALM BEACH ADD. TO
 FBC-2004 SEC 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE BUILDING OFFICIAL.
  