2006-03-18 00:00:00 | PAUL SCHMITZ |
| [email protected] |
| FBC 2004 PLUMBING CODE PLAN REVIEW |
| FBC2004 FUEL GAS CODEPLAN REVIEW |
| FBC 2004 CH 11, FL ACESSIBILITY CODE |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| |
| CHAPT.1, ADMINISTRATION, 2004 EDITION |
| DENIED 2ND TIME |
| 1) |
| 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. |
| CONSTRUCTION DOCUMENTS SHALL BE |
| DIMENSIONED AND DRAWN UPON SUITABLE |
| MATERIAL. ELECTRONIC MEDIA DOUCMENTS ARE |
| PERMITTED TO BE SUBMITTED WHEN APPROVED |
| BY THE BUILDING OFFICAL. CONSTRUCTION |
| DOUCMENTS SHALL BE OF SUFFICENT CLARITY |
| TO INDICATE THE LOCATION, NATURE AND |
| EXTENT OF THE WORK PROPOSED AND SHOW IN |
| DETAIL THAT ITWILL CONFORM TOTHE |
| PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS |
| AS DETERMINED BY THE BUILDING OFFICAL ( |
| SEE ALSO SECTION 106.3.5) |
| |
| 2)TAB 403 MINIMUM FACILITIES. |
| ONE AUTOMATIC CLOTHES WASHER CONNECTION |
| PER DWELING UNIT. |
| 3) SHOW THE FIXTURE CLEARANCE |
| 405.3.1 WATER CLOSETS, URINALS, |
| LAVATORIES AND BIDETS. |
| A WATER CLOSET, URINAL, LAVATORY OR |
| BIDET SHALL NOT BE SET CLOSER THAN 15 |
| INCHES (381 MM) FROM ITS CENTER TO ANY |
| SIDE WALL, PARTITION, VANITY OR OTHER |
| OBSTRUCTION, OR CLOSER THAN 30 INCHES |
| (762 MM) CENTER-TO-CENTER BETWEEN WATER |
| CLOSETS, URINALS OR ADJACENT FIXTURES. |
| THERE SHALL BE AT LEAST A 21-INCH (533 |
| MM) CLEARANCE IN FRONT OF THE WATER |
| CLOSET, URINAL OR BIDET TO ANY WALL, |
| FIXTURE OR DOOR. WATER CLOSET |
| COMPARTMENTS SHALL NOT BE LESS THAN 30 |
| INCHES (762 MM) WIDE OR 60 INCHES (1524 |
| MM) DEEP. THERE SHALL BE AT LEAST A |
| 21-INCH (533 MM) CLEARANCE IN FRONT OF A |
| LAVATORY TO ANY WALL, FIXTURE OR DOOR |
| (SEE FIGURE 405.3.1). |
| 4)BACK FLOW PREVENTER REQUIRED ON WATER |
| SERVICE, LOCAL ORDINANCE #2853-95 |
| |
| END OF COMMENTS, QUESTIONS 561-805-6692 |
| |
| |