Plan Review Notes
Plan Review Notes For Permit 05111120
Permit Number 05111120
Review Stop P
Sequence Number 2
Notes
Date Text
2006-03-18 00:00:00PAUL SCHMITZ
 [email protected]
 FBC 2004 PLUMBING CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE,
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
 DENIED 2ND TIME
 1)
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE
 DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOUCMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED
 BY THE BUILDING OFFICAL. CONSTRUCTION
 DOUCMENTS SHALL BE OF SUFFICENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN
 DETAIL THAT ITWILL CONFORM TOTHE
 PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS
 AS DETERMINED BY THE BUILDING OFFICAL (
 SEE ALSO SECTION 106.3.5)
  
 2)TAB 403 MINIMUM FACILITIES.
 ONE AUTOMATIC CLOTHES WASHER CONNECTION
 PER DWELING UNIT.
 3) SHOW THE FIXTURE CLEARANCE
 405.3.1 WATER CLOSETS, URINALS,
 LAVATORIES AND BIDETS.
 A WATER CLOSET, URINAL, LAVATORY OR
 BIDET SHALL NOT BE SET CLOSER THAN 15
 INCHES (381 MM) FROM ITS CENTER TO ANY
 SIDE WALL, PARTITION, VANITY OR OTHER
 OBSTRUCTION, OR CLOSER THAN 30 INCHES
 (762 MM) CENTER-TO-CENTER BETWEEN WATER
 CLOSETS, URINALS OR ADJACENT FIXTURES.
 THERE SHALL BE AT LEAST A 21-INCH (533
 MM) CLEARANCE IN FRONT OF THE WATER
 CLOSET, URINAL OR BIDET TO ANY WALL,
 FIXTURE OR DOOR. WATER CLOSET
 COMPARTMENTS SHALL NOT BE LESS THAN 30
 INCHES (762 MM) WIDE OR 60 INCHES (1524
 MM) DEEP. THERE SHALL BE AT LEAST A
 21-INCH (533 MM) CLEARANCE IN FRONT OF A
 LAVATORY TO ANY WALL, FIXTURE OR DOOR
 (SEE FIGURE 405.3.1).
 4)BACK FLOW PREVENTER REQUIRED ON WATER
 SERVICE, LOCAL ORDINANCE #2853-95
  
 END OF COMMENTS, QUESTIONS 561-805-6692
  
  