2006-03-17 00:00:00 | ************ UNSAT 2ND REVIEW ********* |
| |
| 1)NOTE: PLEASE KNOW, THERE ARE MANY |
| ELECTRICAL COMMENTS BASED ON SERVICES AS |
| SHOWN, HOWEVER MANY OF THOSE DO NOT |
| APPLY AS THE SERVICES AS SHOWN ARE NOT |
| PERMITTED. PLEASE SEE 230.2, ONLY ONE |
| ELECTRICAL SERIVCE WILL BE PERMITTED. |
| ALL MAINS ARE TO BE GROUPED PER 230.72. |
| PLEASE SEE PTHER COMMENTS AS THEY WILL |
| HAVE AN AFFECT ONE RISER AND NEW |
| SERVICE. |
| |
| 2)NOTE: PLEASE SEE RISER AS SHOWN SHOWS |
| 200A OCP FEEDING 125A PANEL. |
| 240.4, 215.5 ETC. |
| |
| 3)NOTE: PLEASE SEE MISSING EQUIPMENT |
| GROUNDING CONDUCTORS ON ALL CONDUITS ON |
| RISER. |
| |
| 4)NOTE: PLEASE SHOW ALL SERVICE AND |
| PANEL LOCATIONS ON PLANS. |
| 215.5 |
| |
| 5)NOTE: PLEASE KNOW, A HOUSE PANEL WILL |
| BE REQUIRED FOR ANY COMMON AREA BRANCH |
| CIRCUITS. PLEASE KNOW, THE EGRESS |
| LIGHTING ON UPPER FOYER AND STAIRS MAY |
| NOT BE FED FROM ANY ONE UNIT. |
| 210.25 |
| PLEASE ALSO SEE COMMENTS WITH RESPECT TO |
| THE EGRESS LIGHTING AND CONTROL. |
| |
| 6)NOTE: PLEASE SEE LS101-7.8,7.9, |
| NFPA-70 210.70, EGRESS LIGHTING IS |
| REQUIRED AND THE METHOD OF CONTROL CAN |
| BE DECIDED BY THE DESIGNER. PLEASE KNOW |
| HOWEVER , IS USING SWITCHES, THERE MUST |
| ALSO BE 3-WAY SWITCHING AT LOWER LEVEL. |
| PLEASE ALSO SEE 7.9.2.2, 7.8.1.3 WHICH |
| REQUIRES 10FT CANDLES MIN DURING NORMAL |
| OPERATION AND 1 FT CANDLE UNDER |
| EMERGENCY. A BATTERY BACK UP LT OF SOME |
| SORT(S0 WILL BE REQUIRED TO SUPPLY THE |
| MIN OF 1 FT CANDLE UNDER AN EMERGENCY |
| CONDITION. |
| |
| 7)NOTE: PLEASE SEE 424.3B FOR MININUM |
| OCP FOR ALL AHU'S. PLEASE SEE 2-POLE 20A |
| OCP FOR 10KW LOAD? |
| PLEASE SEE 50A OCP FOR 10KW ETC, NONE OF |
| THESE MEET ABOVE CODE. |
| |
| 8)NOTE: PLEASE SEE THE "WALL UNIT" AS |
| SHOWN AND ALSO VERIFY OCP AND UNIT. |
| |
| 9)NOTE: PLEASE PROVIDE ENERGY |
| CALCUALTIONS PER 2004 FBCCHAPTER 13. |
| |
| 10)NOTE: PLEAS PROVIDE SPEC FOR WATER |
| HEATERS BEING SHOWN OUTSIDE IN OPEN AIR. |
| THESE UNIT MUST BERATED FOR WET |
| LOCATIONS, OR OUTDOOR WP ENCLOUSURES |
| SHALL BE SHOWN AND DETAILED. |
| 110.3, 215.5 |
| |
| 11)NOTE: PLEASE SEE SD'S SHALL BE |
| INSTALLED PER NFPA-72 11.8.3.5, NO SD |
| CAN BE WITH-IN 20' OF THE COOKING |
| APPLIANCE UNLESS MEETING THE EXCEPTIONS |
| AS SET-FORTH. PLEASE PROVIDE NOTES FOR |
| TYOE OF SD(S) BEING INSTALLED PER |
| EXCEPTIONS. |
| |
| 12)NOTE: PLEASE SEE THAT PLANS SHALL |
| INDICATE THE CURRENT CODES FOR THIS |
| DESIGN. PLEASE KNOW, WE ARE UNDER THE |
| 2002 NFPA-70, 2002 NFPA-72, 2003 |
| NFPA-101, 2004 FBC. PLANS TO INDICATE |
| THESE AT A MIN. |
| |
| 13)NOTE: PLEASE SEE 2002 NEC 210.12 FOR |
| MIN ARC FAULT PROTECTION REQUIRED FOR |
| ALL CIRCUITING TO SLEEPING ROOMS. |
| RECEPTS, LTS, FANS SD'S ETC. |
| |
| 14)NOTE: PLEASE INDICATE ALL CIRCUITING |
| ON PLANS AND CORRELATE WITH THE |
| SUBMITTED PANEL SCHEDULES. |
| 215.5 |
| |
| 15)NOTE: PLEASE SEE MISSING DEDICATE |
| BATH CIRCUITS PER 210.52D, 210.11C3, |
| SHALL BE 20A AND #12. |
| |
| 16)NOTE: COULD NOT LOCATE ANY MAIN |
| LAUNDRY FACILITIES , PLEASE SEE |
| 210.11C2,210.52F, 220.16 ETC. |
| PLEASE ALSO SEE MIN FACILITIES REQUIRED |
| UNDER THE PLUMB AND MECHANICAL CODE. |
| |
| 17)NOTE: PLEASE SEE FHAR 24 CFR 100.205 |
| FOR ALL DEVICE HEIGHTS AND DEVICE |
| LOCATIONS. THESE ARE TO BE NOTED ON |
| PLANS. |
| |
| 18)NOTE: PLEASE SEE 210.52B1 FOR CIRCUIT |
| REQUIRED IN DINING AREAS AND THE LIKE, |
| THESE SHALL BE ON ONE OR MORE OF THE |
| SMALL APPLIANCE CIRCUITS. |
| |
| 19)NOTE: PLEASE SEE 210.8A FOR GFI |
| LOCATIONS. (BATHRMS) EXISTING OR NEW). |
| |
| 20)NOTE: PLEASE SEE FBC FOR EXSITING |
| BUILDING AND REQUIREMENTS FOR BRINGING |
| ALL UP TO CODE WIHT THE SCOPE OF WORK |
| BEING PERMFORMED. PLEASE SEE THAT THE |
| LEVEL OF ALTERATION SAHLL BE STATED. |
| |
| 21)NOTE: PLEASE SEE LOAD CALCS FOR UNIT |
| "B" WHICH SHOWS NO A/C LOAD IN LOAD |
| CALCUALTIONS, YET PANEL SCHEDULE SHOWS |
| 10KW OF LOAD?? |
| 215.5,424.4,240.4,310.16, ETC. |
| |
| 22)NOTE: PLEASE SEE 250.110, 250.122, |
| 250.24, 250.66 FOR SIZING OF GROUNDING |
| ELECTRODE CONDUCTOR AND EQUIPMENT GRNDS. |
| |
| 23)NOTE: PLEASE SEE PLANS CONTAINING |
| TITLE BLOCKS AND WORK COVERED IN THE |
| REQUIREMENTS OF FS 481.229 ARE REQUIRED |
| TO BE SIGNED , DATED AND SEALED BYB THE |
| REGISTERED ARCHITECT AS LISTED. PLEASE |
| SEE 481.221, FAC 61G1-16.003, .004 |
| |
| 24) NOTE: PLEASE SEE AHU, SHOWS TWO |
| DISCONECTS FOR ONE UNIT?? PLEASE VERIFY |
| AS THIS IS NOT COMMON AND NO CONDUCTOR, |
| DISC SIZE INFORMATION WAS SUPPLIED OR |
| SHOWN. PLEASE ALSO SEE 240.21 AS THESE |
| ARE BEING SHOWN AS "TAPPED" CONDUCTORS?? |
| PLEASE KNOW, THIS SHOULD INDICATE ONE |
| DISCONNECT PER 440.11. |
| 31.16,240.4 ETC. |
| |
| 25)NOTE: PLEASE SEE NO MECHANICAL PLANS |
| WERE SUBMITTED IN ORDER TO VERIFY AND |
| CORRELATE THE EQUIPEMNT, CALCULATIONS |
| ETC. |
| PLEASE SEE FBC 106.3.5.1.1 WHICH |
| DICTATES THE MIN PLANS REQUIRED FOR PLAN |
| REVIEW OF COMMERCIAL BUILDINGS. |
| |
| 26)NOTE: PLEASE SEE THE NOC SUBMITTED |
| HSA SINCE EXPIRED PER FS 713.13(2). IF |
| WORK HAS NOT COMMENCED WITHIN 90 DAYS OF |
| RECORDING NOC, THE NOC SHALL BECOME |
| VOID. |
| |
| ** PLEASE SEE ANY COMMENTS FROM OTHER |
| TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| ** PLEASE SUBMIT THE ABOVE INFORMATION |
| FOR REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |