Plan Review Notes
Plan Review Notes For Permit 05111120
Permit Number 05111120
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-12-28 00:00:00******DENIED******
  
 1) APARTMENT BUILDINGS WITH 3 OR MORE
 UNITS UNDER 1 ROOF REQUIRE HARD WIRED
 SMOKE DETECTORS. PLEASE SHOW ON DRAWINGS
 EVEN IF EXISTING CONDITION.
  
 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE
 REQUIRED TO BE MOUNTED AT DISTANCE NOT
 TO EXCEED 75'.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722