Plan Review Notes For Permit 05111120 |
Permit Number |
05111120 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-12-28 00:00:00 | ******DENIED****** | | | | 1) APARTMENT BUILDINGS WITH 3 OR MORE | | UNITS UNDER 1 ROOF REQUIRE HARD WIRED | | SMOKE DETECTORS. PLEASE SHOW ON DRAWINGS | | EVEN IF EXISTING CONDITION. | | | | 2) 2A-10B,C RATED FIRE EXTINGUISHERS ARE | | REQUIRED TO BE MOUNTED AT DISTANCE NOT | | TO EXCEED 75'. | | | | | | MIKE WENNERGREN, CAPTAIN/WPBFR | | FIRE PLAN REVIEW (561) 805-6722 |
|