Plan Review Notes
Plan Review Notes For Permit 05111120
Permit Number 05111120
Review Stop B
Sequence Number 1
Notes
Date Text
2005-12-21 00:00:001) ACCORDING TO THE DESCRIPTION OF WORK,
 PLANS ARE REQUIRED TO SHOW THE AREA AND
 DETAILS OF WORK.
  
 2) 2001 FL BLD CODE, 1005.4:
 PROVIDE EMERGENCY EGRESS WINDOWS IN
 SLEEPING ROOMS WITH A MINIMUM NET CLEAR
 OPENING HEIGTH OF 24" AND NET CLEAR
 OPENING WIDTH OF 20" AND A NET CLEAR
 OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR
 OPENINGS ARE PERMITTED TO HAVE A NET
 CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH
 SHALL NOT BE MORE THAN 44 " ABOVE THE
 FINISH FLOOR.ALSO A DIAGRAM SHOWING THE
 LAYOUT AND SIZE OF EACH WINDOW IS
 REQUIRED.
  
 3) SHOW IN DETAILS THE WALLS WHICH WILL
 BE REMODLED. THE TYPE OF STUDS WOOD OR
 METAL, THE STUD SPACING ETC.
  
 4) A DETAIL DRAWING FOR THE FLOOR JOIST
 REPAIR IS REQUIRED. SHOW THE SPACING OF
 THE JOISTS/THE CONNECTION/THE TYPE OF
 WOOD/THE SIZE OF JOISTS AND THE
 SHEATHING THICKNESS FOR THE FLOOR.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  
  
  
  