Plan Review Notes For Permit 05111120 |
Permit Number |
05111120 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-12-21 00:00:00 | 1) ACCORDING TO THE DESCRIPTION OF WORK, | | PLANS ARE REQUIRED TO SHOW THE AREA AND | | DETAILS OF WORK. | | | | 2) 2001 FL BLD CODE, 1005.4: | | PROVIDE EMERGENCY EGRESS WINDOWS IN | | SLEEPING ROOMS WITH A MINIMUM NET CLEAR | | OPENING HEIGTH OF 24" AND NET CLEAR | | OPENING WIDTH OF 20" AND A NET CLEAR | | OPENING AREA OF 5.7 SQ.FT. GROUND FLOOR | | OPENINGS ARE PERMITTED TO HAVE A NET | | CLEAR OPENING OF 5.0 SQ. FT. SILL HEIGTH | | SHALL NOT BE MORE THAN 44 " ABOVE THE | | FINISH FLOOR.ALSO A DIAGRAM SHOWING THE | | LAYOUT AND SIZE OF EACH WINDOW IS | | REQUIRED. | | | | 3) SHOW IN DETAILS THE WALLS WHICH WILL | | BE REMODLED. THE TYPE OF STUDS WOOD OR | | METAL, THE STUD SPACING ETC. | | | | 4) A DETAIL DRAWING FOR THE FLOOR JOIST | | REPAIR IS REQUIRED. SHOW THE SPACING OF | | THE JOISTS/THE CONNECTION/THE TYPE OF | | WOOD/THE SIZE OF JOISTS AND THE | | SHEATHING THICKNESS FOR THE FLOOR. | | | | MYRON JACOBS | | BUILDING PLAN REVIEWER | | 805-6726 | | | | | | | | | | | | | | | | |
|