Notes |
Date |
Text |
2006-01-25 00:00:00 | DENIED: | | 1.PLEASE PROVIDE MANUFACTURERS | | SUBMTITTAL DATA FOR THE GENERATOR. | | | | 2.PER NFPA 37 SECTION 4.1.4, ENGINES | | LOCATED OUTDOORS SHALL BE LOCATED AT | | LEAST 5 FT FROM OPENINGS IN WALLS AND 5 | | FT FROM STRUCTURES HAVEING COMBUSTIBLE | | WALLS.AS MINIMUM SEPARATION IS NOT | | REQUIRED IF THE FOLLOWING CONDITIONS ARE | | MET: 1) THE ADJACENT WALL OF THE | | STRUCTURE HAS A FIRE RESISTANCE RATING | | OF AT LEAST 1 HOUR.2)THE WEATHERPROOF | | ENCLOSURE WILL NOT IIGNITE COMBUSTIBLE | | MATERIALS OUTSIDE THE ENCLOSURE. | | | | 3.PLEASE INDICATE DISTANCE OF THE | | GENERATOR EXHAUST TO ANY OPENINGS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT PATTY KRAUSS AT (561)805-6719. |
|