2005-12-24 00:00:00********** UNSAT ***********
  
  
 1)NOTE: PLEASE SEE VALUATION FOR
 PERMITTING AND COMPLETE SCOPE OF WORK
 SHALL INCLUDE ALL LABOR AND MATERIALS.
 PLEASE SEE THE VALUE APPLIED FOR ($5200)
 IS WAY TOO LOW.
 FBC ADMIMISTRATIVE SEC 108.3 AS ADOPTED
 BY THE CITY OF WEST PALM BEACH.
  
 2)NOTE: PLEASE SUBMIT ALL MANUFACTURES
 CUT/SPEC SHEETS FOR SAID GENERATOR, ATS,
 AND SUB-BASE FUEL TANK.
 PLEASE BE SURE ALL LISTINGS ARE SHOWN
 AND ALL ARE LISTED BY A NRTL.
  
 3)NOTE: PLEASE PROVIDE A MEANS OF
 DISCONNECT FOR FEEDERS FROM GEN INT
 EXISTING SERVICE.,
 THIS DISCONNECTING MEANS MUST BE RATED
 FOR LOAD SERVED, SERVICE RATED, GROUPED
 WITH EXISTING MAINS ETC.
 PLEASE SEE 225.31- 225.39.
  
 4)NOTE: PLEASE INCLUDE OCP AT GENERATOR
 IN ORDER TO VERIFY CONDUCTORS, LOADS,
 ETC.
 215.5
  
 5)NOTE: PLEASE PROVIDE COMPLETE LOAD
 CALCUALTIONS FOR SAID LOADS TO BE
 IMPLIED ON GENERATOR.
 PLEASE SEE 702.5, WHICH PERMIT THE
 CUSTOMER TO SELECT LOADS, HOWEVER ON A
 ATS SYSTEM, GENERATOR MUST STILL BE
 RATED FOR ALL LOADS TO BE SERVED.
 PLEASE BE SURE ANY A/C/ HEAT, MOTOR
 LOADS ARE FIGURED AT 100%.
 ** LOAD SHEDDING IS PERMITTED, HOWEVER
 PLEASE SHOW DETAILS IF THIS IS DONE.
  
 6)NOTE: PLEASE KNOW, THE CGC APPLIED TO
 PERMIT IS ONLY PERMITTED TO PLACE SLAB
 AND GEN AND IS NOT PERMITTED TO DO ANY
 OTHER ELECTRICAL WORK.
 PLEASE SEE THAT AN ELECTRICAL CONTRACTOR
 WAS NOT SIGNED ON PERMIT APPLICATION.
  
 ** PLEASE SEE ANY OTHER COMMENTS FROM
 OTHER REVIEWER(S) WHICH MAY AFFECT
 ELECTRICAL PLANS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW