2005-12-24 00:00:00 | ********** UNSAT *********** |
| |
| |
| 1)NOTE: PLEASE SEE VALUATION FOR |
| PERMITTING AND COMPLETE SCOPE OF WORK |
| SHALL INCLUDE ALL LABOR AND MATERIALS. |
| PLEASE SEE THE VALUE APPLIED FOR ($5200) |
| IS WAY TOO LOW. |
| FBC ADMIMISTRATIVE SEC 108.3 AS ADOPTED |
| BY THE CITY OF WEST PALM BEACH. |
| |
| 2)NOTE: PLEASE SUBMIT ALL MANUFACTURES |
| CUT/SPEC SHEETS FOR SAID GENERATOR, ATS, |
| AND SUB-BASE FUEL TANK. |
| PLEASE BE SURE ALL LISTINGS ARE SHOWN |
| AND ALL ARE LISTED BY A NRTL. |
| |
| 3)NOTE: PLEASE PROVIDE A MEANS OF |
| DISCONNECT FOR FEEDERS FROM GEN INT |
| EXISTING SERVICE., |
| THIS DISCONNECTING MEANS MUST BE RATED |
| FOR LOAD SERVED, SERVICE RATED, GROUPED |
| WITH EXISTING MAINS ETC. |
| PLEASE SEE 225.31- 225.39. |
| |
| 4)NOTE: PLEASE INCLUDE OCP AT GENERATOR |
| IN ORDER TO VERIFY CONDUCTORS, LOADS, |
| ETC. |
| 215.5 |
| |
| 5)NOTE: PLEASE PROVIDE COMPLETE LOAD |
| CALCUALTIONS FOR SAID LOADS TO BE |
| IMPLIED ON GENERATOR. |
| PLEASE SEE 702.5, WHICH PERMIT THE |
| CUSTOMER TO SELECT LOADS, HOWEVER ON A |
| ATS SYSTEM, GENERATOR MUST STILL BE |
| RATED FOR ALL LOADS TO BE SERVED. |
| PLEASE BE SURE ANY A/C/ HEAT, MOTOR |
| LOADS ARE FIGURED AT 100%. |
| ** LOAD SHEDDING IS PERMITTED, HOWEVER |
| PLEASE SHOW DETAILS IF THIS IS DONE. |
| |
| 6)NOTE: PLEASE KNOW, THE CGC APPLIED TO |
| PERMIT IS ONLY PERMITTED TO PLACE SLAB |
| AND GEN AND IS NOT PERMITTED TO DO ANY |
| OTHER ELECTRICAL WORK. |
| PLEASE SEE THAT AN ELECTRICAL CONTRACTOR |
| WAS NOT SIGNED ON PERMIT APPLICATION. |
| |
| ** PLEASE SEE ANY OTHER COMMENTS FROM |
| OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |