Plan Review Notes For Permit 05111076 |
Permit Number |
05111076 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-12-09 00:00:00 | *** DENIED *** | | 1) A FIRE DAMPER IS REQUIRED IN EXIST. | | HP DUCT AT NEW FIRE RATED WALL BETWEEN | | SUITE 410 AND 404, PER 2004 FBC 716.5.1 | | . | | 2) NO RETURN AIR GRILL IS SHOWING IN | | ROOM 200. | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | TOM GORDON 805-6729 OR PATTY KRAUSS | | 805-6719. |
|