Plan Review Notes
Plan Review Notes For Permit 05111071
Permit Number 05111071
Review Stop FIRE
Sequence Number 4
Notes
Date Text
2006-12-19 10:26:01*****PROVISO*****
  
  
  
 REVISED PLANS HAVE BEEN APPROVED AND DATE STAMPED.
 PLANS WILL NOT BE RELEASED UNTIL THE FOLLOWING
 CORRECTION HAS BEEN MADE.
  
 *AREA 5, LEVEL 3 STACK SHOWS A SAFETY MARGIN OF 4.703
 PSI.AS PER WPBFR, A SAFETY MARGIN OF AT LEAST 5.0 PSI
 IS REQUIRED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722