2006-06-21 00:00:00 | ******REVISION DENIED****** |
| REFERENCE: FBC-2004 FUEL GAS |
| FBC-2004 CHAPTER 1 |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR THE GAS REVISION: |
| |
| 1. PER FBC-2004 CHAPTER 1, SECTION 106 |
| CONSTRUCTION DOCUMENTS: REVISION |
| DRAWINGS IN PENCIL UNACCEPTABLE |
| 2. PER FBC-2004 CHAPTER 1, SECTION 106.1 |
| CONSTRUCTION DOCUMENTS: MINIMUM OF 2 |
| (TWO) DRAWINGS REQUIRED FOR REVISION. |
| (NOTE: ONLY ONE REVISION DRAWING |
| SUBMITTED IN PENCIL) |
| 3. PER FBC-2004 CHAPTER 1 |
| 106.1.1 INFORMATION ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE |
| AND RELAVENT LAWS, ORDINANCES, RULES AND |
| REGULATIONS, AS DETERMINED BY THE |
| BUILDING OFFICIAL.(NOTE: WHERE THE 1" PE |
| BELOW GRADE IS INDICATED ON THE REVISION |
| THE TRANSITION TO ABOVE GROUND GALVAN- |
| IZED NEEDS TO BE INDICATED ON REVISION) |
| 4. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE.(NOTE: THERE ARE NO |
| CORRESPONDING LENGTHS INDICATED ON THE |
| REVISION DRAWING) |
| 5. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, AND ALL PIPE SIZES.(NOTE: THE |
| ONLY MATERIAL INDICATED ON REVISION IS |
| THE UNDERGROUND PE, THE ABOVE GROUND |
| GALVANIZED MATERIAL NEEDS TO BE |
| INDICATED ON REVISION DRAWING) |
| 6. PER FBC-2004 FUEL GAS, SECTION 409.4. |
| A LISTED SHUT OFF VALVE SHALL BE |
| INSTALLED IMMEDIATELY AHEAD OF EACH MP |
| REGULATOR. PLEASE SEE CORRECTED REVISION |
| DRAWING FOR REFERENCE FOR RESUBMITTAL. |
| 7. FBC-2004 FUEL GAS SEC. 404.12 OUTLET |
| CLOSURES: GAS OUTLETS THAT DO NOT CON- |
| NECT TO APPLIANCES SHALL BE CAPPED GAS |
| TIGHT.(NOTE: ON 2LB SYSTEMS SHUT OFF |
| VALVE AND REGULATOR SHALL BE INSTALLED |
| ON FUTURE APPLIANCES FOR FINAL, PLEASE |
| SEE CORRECTED DRAWING FOR REFERENCE FOR |
| RESUBMITTAL) |
| |
| **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| |
| END OF COMMENTS: |
| |