2006-06-21 00:00:00******REVISION DENIED******
 REFERENCE: FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR THE GAS REVISION:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106
 CONSTRUCTION DOCUMENTS: REVISION
 DRAWINGS IN PENCIL UNACCEPTABLE
 2. PER FBC-2004 CHAPTER 1, SECTION 106.1
 CONSTRUCTION DOCUMENTS: MINIMUM OF 2
 (TWO) DRAWINGS REQUIRED FOR REVISION.
 (NOTE: ONLY ONE REVISION DRAWING
 SUBMITTED IN PENCIL)
 3. PER FBC-2004 CHAPTER 1
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL.(NOTE: WHERE THE 1" PE
 BELOW GRADE IS INDICATED ON THE REVISION
 THE TRANSITION TO ABOVE GROUND GALVAN-
 IZED NEEDS TO BE INDICATED ON REVISION)
 4. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.(NOTE: THERE ARE NO
 CORRESPONDING LENGTHS INDICATED ON THE
 REVISION DRAWING)
 5. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, AND ALL PIPE SIZES.(NOTE: THE
 ONLY MATERIAL INDICATED ON REVISION IS
 THE UNDERGROUND PE, THE ABOVE GROUND
 GALVANIZED MATERIAL NEEDS TO BE
 INDICATED ON REVISION DRAWING)
 6. PER FBC-2004 FUEL GAS, SECTION 409.4.
 A LISTED SHUT OFF VALVE SHALL BE
 INSTALLED IMMEDIATELY AHEAD OF EACH MP
 REGULATOR. PLEASE SEE CORRECTED REVISION
 DRAWING FOR REFERENCE FOR RESUBMITTAL.
 7. FBC-2004 FUEL GAS SEC. 404.12 OUTLET
 CLOSURES: GAS OUTLETS THAT DO NOT CON-
 NECT TO APPLIANCES SHALL BE CAPPED GAS
 TIGHT.(NOTE: ON 2LB SYSTEMS SHUT OFF
 VALVE AND REGULATOR SHALL BE INSTALLED
 ON FUTURE APPLIANCES FOR FINAL, PLEASE
 SEE CORRECTED DRAWING FOR REFERENCE FOR
 RESUBMITTAL)
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721
  
  
  
  
  
  