Plan Review Notes For Permit 05111003 |
Permit Number |
05111003 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-12-01 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05111003 | | ADD: 701 NORTHPOINTE PARKWAY | | CONT: PASS INTERNATIONAL | | TEL: (954)421-9000 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | | | 1) PROVIDE NOC RECORDED WITH THE CLERK | | OF COURT BEFORE A PERMIT CAN BE ISSUED. | | | | 2) 803.5 INTERIOR FINISH REQUIREMENTS | | BASED ON GROUP. | | INTERIOR WALL AND CEILING FINISH SHALL | | HAVE A FLAME SPREAD INDEX NOT GREATER | | THAN THAT SPECIFIED IN TABLE 803.5 FOR | | THE GROUP AND LOCATION DESIGNATED. | | INTERIOR WALL AND CEILING FINISH | | MATERIALS, OTHER THAN TEXTILES, TESTED | | IN ACCORDANCE WITH NFPA 286 AND MEETING | | THE ACCEPTANCE | | | | 3) MISSING REQUIREMENTS FOUND UNDER THE | | 2004 CODE: | | 3A) THE EDITION OF THE CODE UNDER WHICH | | THE PERMIT WAS ISSUED. | | 3B)THE USE AND OCCUPANCY, IN | | ACCORDANCE WITH THE PROVISIONS OF | | CHAPTER 3 . | | 3C)THE TYPE OF CONSTRUCTION AS DEFINED | | IN CHAPTER 6 . | | 3D) THE DESIGN OCCUPANT LOAD. | | 3E)IF AN AUTOMATIC SPRINKLER SYSTEM IS | | PROVIDED, WHETHER THE SPRINKLER SYSTEM | | IS REQUIRED. | | 3F) ANY SPECIAL STIPULATIONS AND | | CONDITIONS OF THE BUILDING PERMIT. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 | | | | |
|